Inspections for the day of: Friday, May 14, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00254 INSP-Alarm Testing5/12/20045/14/20045/14/2004 12:00:00 AMAPASS
fire life safety finaled 5/14/2004 8:11:51 AM
MIS04-00083 FIR-Final5/13/20045/14/20045/14/2004 12:00:00 AMAPART
Temporary occupancy given until the exit sign is repaired and the thumbturn is removed from the rear exterior door. 5/14/2004 11:23:29 AM
FIR04-00267 INSP-Final Inspection5/13/20045/14/20045/14/2004 12:00:00 AMAPART
A temporary occupancy was given with dave millers permission as long as a 24-hr/7-day/wk fire watch is in place until the fire alarm system has been finaled. Per Chris with Dollar Tree, United Security (###-####) has been hired. Items to be corrected include: Sample tubes on the duct smoke detectors are too short. Provide correct lenght tubes. Provide tamper switches on all anti-freeze loop control valves. Resubmit plans showing the additional control valve in the Dollar Tree space. Provide building map with correct device addresses. Provide cover on the electrical connections for the FACP. Provide connection to the hood suppression system and test. PIV supervisory signal lactched. Change to non-latching. Provide minimum 8.4 AH battery for the 12-volt side of the FACP. Test flow switch. Monitoring company does not have account set up for new alarm system/device addresses. Get account set up and retest all devices prior to calling for final inspection. 5/14/2004 1:47:12 PM
FIR04-00254 INSP-Final Inspection5/14/20045/14/20045/14/2004 12:00:00 AMAPASS
fire alarm finaled
BLD04-00446 FIRE-Final Inspection5/14/20045/14/20045/14/2004 12:00:00 AMAPASS
fire life safety finaled