FIR06-00888
| FIR-Aging Inspection | 5/14/2007 | 5/14/2007 | 5/21/2007 12:43:26 PM | | DONE |
|
|
Building under construction, work in progress.
|
FIR07-00365
| INSP-Sprinkler Rough-in | 5/11/2007 | 5/14/2007 | 5/14/2007 6:01:39 PM | P | PASS |
|
|
Corrections are complete, final FS inspection passed.
|
BLD06-02465
| FIRE-Final Inspection | 5/14/2007 | 5/14/2007 | 5/14/2007 5:59:18 PM | P | FAIL |
|
|
Need to install one exit sign as discussed, the project related fire sprinkler permit must be finaled prior to life safety final.
|
FIR06-00770
| INSP-Final Inspection | 5/14/2007 | 5/14/2007 | 5/14/2007 5:57:44 PM | P | FAIL |
|
|
Overspaced heads at one hallway, missing escutcheon at one location.
|
FIR06-00986
| INSP-Sprinkler Rough-in/Hydro | 5/11/2007 | 5/14/2007 | 5/14/2007 1:57:36 PM | P | PART |
|
|
OH hydrostatic test for the west building (bld#1) passed.
|
FIR07-00286
| INSP-Final Inspection | 5/14/2007 | 5/14/2007 | 5/14/2007 12:43:01 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00286
| INSP-Final Inspection | 5/14/2007 | 5/14/2007 | 5/14/2007 12:28:10 PM | P | DONE |
|
|
Duplicate inspection request.
|
FIR07-00387
| INSP-Final Inspection | 5/11/2007 | 5/14/2007 | 5/14/2007 12:26:24 PM | A | PASS |
|
|
Fire alarm testing completed, inspection passed, permit finaled.
|
FIR06-01010
| INSP-Sprinkler Rough-in | 5/11/2007 | 5/14/2007 | 5/14/2007 12:25:16 PM | A | PART |
|
|
OH hydrostatic test for the 2nd and 3rd floors both passed inspection.
|
FIR06-01016
| INSP-Sprinkler Rough-in | 5/11/2007 | 5/14/2007 | 5/14/2007 11:15:15 AM | A | FAIL |
|
|
Overspaced heads at the front service area, ATR too close to an upright at the mech. room, no access to one locked room, DP at the cooler and outside canopy are not yet installed.
|
BLD06-00875
| FIRE-Final Inspection | 5/11/2007 | 5/14/2007 | 5/14/2007 11:12:33 AM | A | FAIL |
|
|
Need approved plans on site for review, missing door hardware, also need to supply one 2A10BC fire extinguisher for the storage area.
|