Inspections for the day of: Monday, May 14, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00888 FIR-Aging Inspection5/14/20075/14/20075/21/2007 12:43:26 PM DONE
Building under construction, work in progress.
FIR07-00365 INSP-Sprinkler Rough-in5/11/20075/14/20075/14/2007 6:01:39 PMPPASS
Corrections are complete, final FS inspection passed.
BLD06-02465 FIRE-Final Inspection5/14/20075/14/20075/14/2007 5:59:18 PMPFAIL
Need to install one exit sign as discussed, the project related fire sprinkler permit must be finaled prior to life safety final.
FIR06-00770 INSP-Final Inspection5/14/20075/14/20075/14/2007 5:57:44 PMPFAIL
Overspaced heads at one hallway, missing escutcheon at one location.
FIR06-00986 INSP-Sprinkler Rough-in/Hydro5/11/20075/14/20075/14/2007 1:57:36 PMPPART
OH hydrostatic test for the west building (bld#1) passed.
FIR07-00286 INSP-Final Inspection5/14/20075/14/20075/14/2007 12:43:01 PMPPASS
Fire sprinkler permit finaled.
FIR07-00286 INSP-Final Inspection5/14/20075/14/20075/14/2007 12:28:10 PMPDONE
Duplicate inspection request.
FIR07-00387 INSP-Final Inspection5/11/20075/14/20075/14/2007 12:26:24 PMAPASS
Fire alarm testing completed, inspection passed, permit finaled.
FIR06-01010 INSP-Sprinkler Rough-in5/11/20075/14/20075/14/2007 12:25:16 PMAPART
OH hydrostatic test for the 2nd and 3rd floors both passed inspection.
FIR06-01016 INSP-Sprinkler Rough-in5/11/20075/14/20075/14/2007 11:15:15 AMAFAIL
Overspaced heads at the front service area, ATR too close to an upright at the mech. room, no access to one locked room, DP at the cooler and outside canopy are not yet installed.
BLD06-00875 FIRE-Final Inspection5/11/20075/14/20075/14/2007 11:12:33 AMAFAIL
Need approved plans on site for review, missing door hardware, also need to supply one 2A10BC fire extinguisher for the storage area.