FIR07-00268
| INSP-Final Inspection | 5/14/2007 | 5/14/2007 | 5/14/2007 4:36:00 PM | P | PASS |
|
|
Permit finaled
|
BLD07-00771
| FIRE-Final Inspection | 5/14/2007 | 5/14/2007 | 5/14/2007 4:04:45 PM | P | PASS |
|
|
life safety passed
|
FIR07-00366
| INSP-Final Inspection | 5/11/2007 | 5/14/2007 | 5/14/2007 4:00:20 PM | A | PASS |
|
|
permit finaled
|
FIR07-00130
| INSP-Sprinkler Rough-in/Hydro | 5/11/2007 | 5/14/2007 | 5/14/2007 1:02:04 PM | A | FAIL |
|
|
The attic sprinkler system still does not match the approved plans with upright heads overspaced and too far from the deck and earthquake bracing missing. The third floor wet system hangers and tenting have been corrected. The second floor hangers have been corrected. The contractor stated that all of the plan deviations that I marked in red on the city approved plans were ok with Brian and no resubmittals required. I called Brian and he stated that was not the case. I left a correction notice with the fitter stating that resubmittals are required. I gave the fitter permission for only the second floor piping and the piping in the first floor resident rooms to be covered. All other piping is to remain uncovered until it matches the city approved plans or resubmittals are approved. The first floor and second floor hydro tests passed. The third floor hydro test failed. These floors had to be retested due to the main piping being the wrong size. I also aske the fitter for verification that the 3" sch 10 piping could be used incase the piping was submitted as plastic. The plans were not clear about this.
|
BLD06-03440
| FIRE-Final Inspection | 5/11/2007 | 5/14/2007 | 5/14/2007 10:21:38 AM | A | PASS |
|
|
life safety passed
|
FIR06-00536
| INSP-Final Inspection | 5/11/2007 | 5/14/2007 | 5/14/2007 10:20:59 AM | A | PASS |
|
|
permit finaled
|