FIR06-00620
| INSP-Alarm Testing | 5/12/2008 | 5/14/2008 | 5/14/2008 5:03:23 PM | A | PART |
|
|
Testing for the second floor AHU duct detectors completed okay as noted on plans with the exception of address changes at three locations and sample tubes to be extended as necessary for red-lined locations.
|
FIR07-00812
| INSP-Sprinkler Rough-in/Hydro | 5/13/2008 | 5/14/2008 | 5/14/2008 4:58:05 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory, UG hydrostatic test is not ready at this time due to pressure loss during initial pretest per contractor.
|
FIR08-00280
| INSP-Final Inspection | 5/13/2008 | 5/14/2008 | 5/14/2008 4:55:22 PM | A | PASS |
|
|
Fire sprinkler work per scope of this permit passed final inspection.
|
FIR08-00129
| INSP-Final Inspection | 5/13/2008 | 5/14/2008 | 5/14/2008 12:27:53 PM | A | PASS |
|
|
Testing for the remainder of alarm work completed today including clean agent panel monitoring, flows and tampers at the eight existing risers and two antifreeze loops, two duct detectors reprogramed correctly while on site, repaired incorrectly programed pressure switch at the floral shop riser, c/n items revised, FACP tested okay, signals verified, map provided including changes, permit finaled.
|
FIR08-00172
| INSP-Final Inspection | 5/14/2008 | 5/14/2008 | 5/14/2008 12:17:27 PM | A | PASS |
|
|
Functional testing of the new horn and relocated annunciator completed acceptable, fire alarm permit finaled.
|
FIR08-00283
| INSP-Final Inspection | 5/14/2008 | 5/14/2008 | 5/14/2008 12:15:19 PM | A | PASS |
|
|
New fire sprinkler work passed final inspection, need to repair sheetrock where the 2" line passes through the shop ceiling.
|
FIR08-00283
| FIR-Aging Inspection | 5/13/2008 | 5/14/2008 | 5/14/2008 12:11:48 PM | A | DONE |
|
|
Permit scheduled for final as needed.
|
BLD08-01013
| FIRE-Final Inspection | 5/13/2008 | 5/14/2008 | 5/14/2008 12:11:00 PM | A | FAIL |
|
|
No permit documents on site for review, discussed general requirements with the owner and some specific issues to be corrected including missing "door to remain unlocked...." signage, missing building address numbers, need to post one certified/tagged fire extinguisher, door hardware at the second exit and restroom is not approved, repair and provide exit signage as discussed.
|