Inspections for the day of: Wednesday, May 14, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00750 Rough-In Permanent Service5/13/20085/14/20085/14/2008 4:50:09 PMPPART
steve Phone #: ###-#### ok cover walls only service not ready grounding & bonding not completed
ELE08-01224 Electrical Rough-In5/14/20085/14/20085/14/2008 3:08:25 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Robert Murray ok cover ri on addition area only
ELE08-01188 Final5/14/20085/14/20085/14/2008 12:23:34 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla they opened the walls ok final
ELE08-00905 Electrical Rough-In5/13/20085/14/20085/14/2008 11:54:01 AMAPASS
ben Phone #: ###-#### ok cover ri
ELE08-01236 Final5/13/20085/14/20085/14/2008 8:43:54 AMAFAIL
keith Phone #: ###-#### correction nec250 grounding & grounded conductors shall installed on the same bus bar
ELE08-01235 Electrical Rough-In5/13/20085/14/20085/14/2008 8:12:41 AMANH
Door will be unlocked. Old curves store Phone #: ###-#### Internet Inspection Request from: William Zerfas no access reinspection fee callled left message