FIR08-00786
| INSP-Alarm Testing | 5/13/2009 | 5/14/2009 | 5/15/2009 11:40:07 AM | A | PART |
|
|
See permit activity comments for work completed to date.
|
BLD08-01994
| FIRE-Final Inspection | 5/14/2009 | 5/14/2009 | 5/15/2009 7:38:20 AM | P | FAIL |
|
|
Project is not ready for final, missing several items, see plans and fire code review notes for details.
|
BLD08-01993
| FIRE-Final Inspection | 5/14/2009 | 5/14/2009 | 5/14/2009 3:05:30 PM | P | FAIL |
|
|
Missing fire extinguishers, need to post building address, door hardware at two locations in the clubhouse is not approved, fire dept. access is not complete, see stamped plan and fire code review notes for detailed requirements.
|
BLD08-02383
| FIRE-Final Inspection | 5/14/2009 | 5/14/2009 | 5/14/2009 3:01:25 PM | P | PART |
|
|
EM lights and exit signs tested okay, fire life safety approved for final pending completion of fire alarm permit work.
|
FIR09-00182
| INSP-Alarm Testing | 5/13/2009 | 5/14/2009 | 5/14/2009 3:00:01 PM | A | FAIL |
|
|
Duct detector at the conference room 2nd floor needs to shut down power to the HVAC unit immediately upon smoke detection, missing mag lock interconnection relay to drop power to the door locks upon fire alarm activation.
|
BLD05-01680
| FIRE-Conference | 5/14/2009 | 5/14/2009 | 5/14/2009 11:51:25 AM | P | DONE |
|
|
Regarding alarm and sprinkler permit work, discussed PFE location.
|
FIR09-00236
| INSP-Final Inspection | 5/14/2009 | 5/14/2009 | 5/14/2009 11:48:30 AM | A | FAIL |
|
|
Upright sprinkler protection above the hard lid ceilings are overspaced.
|
BLD08-02581
| FIRE-Final Inspection | 5/13/2009 | 5/14/2009 | 5/14/2009 11:21:03 AM | A | PASS |
|
|
Fire life safety per the scope of work passed inspection.
|
BLD09-00647
| FIRE-Final Inspection | 5/13/2009 | 5/14/2009 | 5/14/2009 10:21:52 AM | A | PASS |
|
|
Items on correction notice verified for completion, life safety finaled.
|
BLD08-02589
| FIRE-Final Inspection | 5/14/2009 | 5/14/2009 | 5/14/2009 9:51:34 AM | P | PASS |
|
|
Life safety inspection completed satisfactory, mag lock override switches tested okay.
|