Inspections for the day of: Thursday, May 14, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00786 INSP-Alarm Testing5/13/20095/14/20095/15/2009 11:40:07 AMAPART
See permit activity comments for work completed to date.
BLD08-01994 FIRE-Final Inspection5/14/20095/14/20095/15/2009 7:38:20 AMPFAIL
Project is not ready for final, missing several items, see plans and fire code review notes for details.
BLD08-01993 FIRE-Final Inspection5/14/20095/14/20095/14/2009 3:05:30 PMPFAIL
Missing fire extinguishers, need to post building address, door hardware at two locations in the clubhouse is not approved, fire dept. access is not complete, see stamped plan and fire code review notes for detailed requirements.
BLD08-02383 FIRE-Final Inspection5/14/20095/14/20095/14/2009 3:01:25 PMPPART
EM lights and exit signs tested okay, fire life safety approved for final pending completion of fire alarm permit work.
FIR09-00182 INSP-Alarm Testing5/13/20095/14/20095/14/2009 3:00:01 PMAFAIL
Duct detector at the conference room 2nd floor needs to shut down power to the HVAC unit immediately upon smoke detection, missing mag lock interconnection relay to drop power to the door locks upon fire alarm activation.
BLD05-01680 FIRE-Conference5/14/20095/14/20095/14/2009 11:51:25 AMPDONE
Regarding alarm and sprinkler permit work, discussed PFE location.
FIR09-00236 INSP-Final Inspection5/14/20095/14/20095/14/2009 11:48:30 AMAFAIL
Upright sprinkler protection above the hard lid ceilings are overspaced.
BLD08-02581 FIRE-Final Inspection5/13/20095/14/20095/14/2009 11:21:03 AMAPASS
Fire life safety per the scope of work passed inspection.
BLD09-00647 FIRE-Final Inspection5/13/20095/14/20095/14/2009 10:21:52 AMAPASS
Items on correction notice verified for completion, life safety finaled.
BLD08-02589 FIRE-Final Inspection5/14/20095/14/20095/14/2009 9:51:34 AMPPASS
Life safety inspection completed satisfactory, mag lock override switches tested okay.