Inspections for the day of: Thursday, May 14, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00105 FIRE-Final Inspection5/13/20095/14/20095/14/2009 1:29:42 PMAFAIL
Provide single action hardware on the restroom door, remove the deadbolt on the north west exit door, provide sticker at teh main exit door as discussed.
FIR06-00205 INSP-Final Inspection5/13/20095/14/20095/14/2009 12:31:33 PMAPASS
Permit finaled
FIR05-00861 INSP-Final Inspection5/13/20095/14/20095/14/2009 12:31:15 PMAPASS
Permit finaled
FIR05-00322 INSP-Final Inspection5/13/20095/14/20095/14/2009 12:30:48 PMAPASS
Permit finaled
BLD09-00427 FIRE-Conference5/13/20095/14/20095/14/2009 10:07:10 AMADONE
I contacted Layton construction about the attached FIR permit. Per the BLD permit all of the work is on the third floor. The attached FIR is for work on the second floor that they are not a part of.
FIR08-00776 INSP-Alarm Testing5/13/20095/14/20095/14/2009 10:05:40 AMAPASS
Four smoke detectors and one manual pull station were tested. They are located in phase 5, sub phase 4 and 5. See the city approved plans with todays date and my name written at each device. Items tested ok.
BLD08-02589 FIRE-Final Inspection5/13/20095/14/20095/14/2009 8:25:17 AMAFAIL
Tried to contact Toby and left two voice messages. No inspection was perform and there was no access to the building.