Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00142 ELE-Aging Inspection5/14/20105/14/20105/18/2010 4:58:21 AM DONE
see doc expire
ELE07-04036 ELE-Aging Inspection5/14/20105/14/20105/18/2010 4:57:09 AM DONE
see doc expire
ELE08-03008 ELE-Aging Inspection5/14/20105/14/20105/18/2010 4:54:44 AM DONE
see doc expire
ELE05-00955 ELE-Aging Inspection5/14/20105/14/20105/17/2010 6:26:28 AM DONE
see doc expire
ELE05-00204 ELE-Aging Inspection5/14/20105/14/20105/17/2010 6:23:05 AM DONE
see doc expire
ELE10-00680 Electrical Rough-In5/14/20105/14/20105/14/2010 3:39:15 PMPPASS
underground Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g parking lot
ELE10-01033 Rough-In Permanent Service5/14/20105/14/20105/14/2010 2:37:58 PMPPASS
Inspection requested from web by: Stephen Kren Phone #: ###-#### corrections made, ric ok, p/s u/g n ok
ELE10-00959 Rough-In Permanent Service5/14/20105/14/20105/14/2010 2:06:37 PMPPASS
stu - ###-#### p/s, exst meter pak, n, ok, 1 meter only
ELE04-03346 DOC - Permit Expired5/14/20105/14/20105/14/2010 12:03:51 PMPPASS
no activity, ok to doc expire
ELE04-01869 DOC - Permit Expired5/14/20105/14/20105/14/2010 12:02:09 PMPPASS
no activity, ok to doc expire
ELE04-00644 DOC - Permit Expired5/14/20105/14/20105/14/2010 12:00:38 PMPPASS
no activity, ok to doc expire
ELE04-00332 DOC - Permit Expired5/14/20105/14/20105/14/2010 11:59:02 AMPPASS
no activity, ok to doc expire
ELE04-00521 DOC - Permit Expired5/14/20105/14/20105/14/2010 11:57:16 AMPPASS
no activity, ok to doc expire
ELE04-03102 DOC - Permit Expired5/14/20105/14/20105/14/2010 11:55:47 AMPPASS
no activity, ok to doc expire
ELE03-03348 DOC - Permit Expired5/14/20105/14/20105/14/2010 11:54:08 AMPPASS
no activity, ok to doc expire
ELE03-03289 DOC - Permit Expired5/14/20105/14/20105/14/2010 11:52:37 AMPPASS
no activity, ok to doc expire
ELE10-00423 Rough-In Permanent Service5/13/20105/14/20105/14/2010 10:28:22 AMAPASS
Inspection requested from web by: Clint Tate Phone #: ###-#### ri ok, p/s u/g n ok
ELE10-00922 Rough-In Permanent Service5/13/20105/14/20105/14/2010 10:06:50 AMAFAIL
Roy 866 2532 met contractor, NEC 314.23 shall provide propery sized pull box at service for angle pull
ELE10-00680 Electrical Rough-In5/13/20105/14/20105/14/2010 9:47:45 AMAPASS
underground Inspection requested from web by: Mark Sessions Phone #: ###-#### ok to cover u/g north and middle parking lot
ELE10-01033 Rough-In Permanent Service5/13/20105/14/20105/14/2010 8:21:29 AMAFAIL
Thanks, Terry W. Inspection requested from web by: Stephen Kren Phone #: ###-#### called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC shall provide boxes for wiring terminations, master bath, data, shall provide available fault current from ipco, NOTE corrections shall be made within 5 working days or further action will be taken
ELE10-00719 Final5/13/20105/14/20105/13/2010 8:52:21 AMACANC
Final inspection needed Inspection requested from web by: jon gleason Phone #: ###-#### Inspection cancelled from web by: jon gleason