Inspections for the day of: Tuesday, May 14, 2013.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02317 FIRE-Final Inspection5/9/20135/14/20135/14/2013 6:09:49 PMPPART
Completed walkthrough of work completed to date including the basement and 1st thru 4th floors. Refer to corrections list for items noted in need of adjustment, repair or provision.
FIR13-00068 INSP-Sprinkler Rough-in5/13/20135/14/20135/14/2013 6:06:10 PMPPART
Refer to clouded, initialed and dated locations on approved plan set for grid ceiling rooms and areas okayed for cover. Noted three missing uprights and one missing hanger above two rooms. Several areas now have grid ceilings where plans indicate open to structure. Painted upright heads will need to be replaced per NFPA 13 requirements.
BLD12-03321 FIRE-Conference5/14/20135/14/20135/14/2013 6:00:10 PMPDONE
Regarding project related FIR trade permit work.
FIR12-00550 INSP-Sprinkler Rough-in/Hydro5/14/20135/14/20135/14/2013 5:59:18 PMAPART
Phases one and two as indicated on approved plans okayed for cover.
FIR12-00551 INSP-Final Inspection5/14/20135/14/20135/14/2013 5:58:28 PMAPART
Final pending ceiling finishes