MEC18-03534
| Final | 5/13/2019 | 5/14/2019 | 5/14/2019 11:36:25 AM | A | FAIL |
|
|
We would like to request a final inspection for rooms 115-323 for tomorrow AM please. Call Caleb before coming out at ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery - Still need LEED's prelimanary commisioning report submitted to Building Official prior to occupancy. Need a permanent ladders in place for accessing equipment on roof per IMC 306.5
|
MEC18-04797
| Rough-in | 5/13/2019 | 5/14/2019 | 5/14/2019 11:00:25 AM | A | PART |
|
|
Rough Cover units 511-515 // Call Curt ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery - 512, 514, 515 okay to cover. 511, and 513 exhaust air needs to terminate 10' away or 3' above fresh air intake
|