Inspections for the day of: Thursday, May 14, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04376 Final5/8/20205/14/20205/14/2020 2:15:32 PMPPASS
Swimming pool electrical final Phone #: ###-#### Inspection requested via web by Kevin Koomler Final ok
ELE20-01562 Electrical Rough-In5/13/20205/14/20205/14/2020 11:40:56 AMAPASS
Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
Called and had attached to BLD20-00379.
Added a drinking fountain receptacle off existing GFCI circuit on other side of wall.
Wall rough in ok cover
ELE20-00073 Electrical Rough-In5/13/20205/14/20205/14/2020 11:14:21 AMANR
ok video/ photo // Ben Phone #: ###-#### Circuits needed in kitchen for hood, and appliances on opposite wall. additional areas need attention, loose wiring, ect. Interior not ready, called and had atteched to BLD20-00315.
ELE20-00073 Permanent Service5/14/20205/14/20205/14/2020 11:09:03 AMPPASS
ok video/ photo // Ben Phone #: ###-#### p/s o/h rec ok
ELE20-01623 Permanent Service5/14/20205/14/20205/14/2020 10:37:51 AMAPASS
Inspection for Energize Service. Please call Caleb with any questions or concerns. Lock Box code is 1776. Phone #: ###-#### Inspection requested via web by Caleb Gaylord Full rewire, banch circuits not in panel at time of inspection. p/s o/h rec ok
ELE20-01641 Rough-In Permanent Service5/13/20205/14/20205/14/2020 9:46:03 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kevin Heideman
Foam seal done prior to inspection, contractor apologized.
300.4- Nail plate needed left of panel down low. 314.25- Recessed can covers shall be installed to totally cover opening. 1 kitchen, kitchen over sink, front entry,
* cover missing on out entry can