Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-01127 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPASS
VERN; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 5/15/2003 12:50:50 PM
ELE02-01011 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok needs proper rated phone cable in cabinet 5/15/2003 12:10:42 PM
ELE02-01009 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok needs proper rated phone cable in cabinet 5/15/2003 12:11:47 PM
ELE02-01006 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok needs proper rated phone cable on cabinet 5/15/2003 12:12:34 PM
ELE02-01005 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok needs proper rated phone cable in cabinet 5/15/2003 12:13:21 PM
ELE02-01004 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok 314.3 needs bond bushings on metallic raceways 5/15/2003 12:15:19 PM
ELE02-01018 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok 314.3 needs bond bushings on metallic raceways 5/15/2003 12:16:06 PM
ELE02-01019 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok 314.3 needs bond bushings metallic raceways 5/15/2003 12:16:44 PM
ELE02-01017 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok 314.3 needs bond bushing for metallic raceway 5/15/2003 3:09:32 PM
ELE02-01016 Final5/14/20035/15/20035/15/2003 12:00:00 AMAPART
###-#### blake temp ok 314.3 needs bond bushing metallic raceway 5/15/2003 3:10:09 PM
ELE03-01406 Rough-In Permanent Service5/14/20035/15/20035/15/2003 12:00:00 AMAFAIL
KEVIN; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted called 300.4(A)(1)&(D)110.3(B) too many cables under staples,334.30 cables on edge 800.6 and 312.5 for low voltage wiring 5/15/2003 9:06:47 AM
ELE03-01055 Permanent Service5/14/20035/15/20035/15/2003 12:00:00 AMPFAIL
###-#### back door unlocked or call for access cor. posted called 250.92(A)(3) bond both ends of nipple between meter and panel, 250.104(A)(1) jumper around dielectric union in basement, 110.26(F)(1) clearence sub panel in basement, use manufactures listed equip grd bus 5/15/2003 2:09:46 PM
ELE03-00907 Final5/15/20035/15/20035/15/2003 12:00:00 AMPPASS
MARK; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 5/15/2003 4:19:11 PM
ELE03-01406 Rough-In Permanent Service5/15/20035/15/20035/15/2003 12:00:00 AMPPASS
###-#### cor. made r/i ok

p/s u/g new ok 5/15/2003 3:48:36 PM