ELE05-04313
| ELE-Aging Inspection | 5/15/2006 | 5/15/2006 | 5/19/2006 9:56:38 AM | | DONE |
|
|
see final
|
ELE06-01692
| Permanent Service | 5/12/2006 | 5/15/2006 | 5/15/2006 4:30:14 PM | P | NR |
|
|
tim ###-#### still didn't have original panel out of wall, went back later, nh, called and they were getting pipe cut. Told owner to call tomorrow when ready.They have a gen set for freezer.
|
ELE05-03620
| Final | 5/15/2006 | 5/15/2006 | 5/15/2006 3:58:40 PM | P | PASS |
|
|
Kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE06-01486
| Rough-In Permanent Service | 5/15/2006 | 5/15/2006 | 5/15/2006 3:25:51 PM | P | PASS |
|
|
Kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok, p/s u/g n ok
|
ELE05-02631
| ELE-Aging Inspection | 5/15/2006 | 5/15/2006 | 5/15/2006 2:47:56 PM | | NR |
|
|
no call for final, suc
|
ELE06-00510
| ELE-Aging Inspection | 5/15/2006 | 5/15/2006 | 5/15/2006 2:23:38 PM | | DONE |
|
|
see final
|
ELE06-00510
| Final | 5/15/2006 | 5/15/2006 | 5/15/2006 2:23:16 PM | P | PASS |
|
|
looked at sign, ok to final
|
ELE06-01702
| Electrical Rough-In | 5/15/2006 | 5/15/2006 | 5/15/2006 2:01:03 PM | P | PASS |
|
|
###-#### - mike ok to cover front porch ceilings only
|
ELE06-01678
| Rough-In Permanent Service | 5/15/2006 | 5/15/2006 | 5/15/2006 1:16:53 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook corr made, ric ok, p/s u/g n ok
|
ELE06-01082
| Final | 5/12/2006 | 5/15/2006 | 5/15/2006 11:39:20 AM | A | PASS |
|
|
Please call if you have any questions and/or concerns; Phone #: ###-#### Internet Inspection Request from: Eric Shaner lookrd at sign, ok to final
|
ELE06-01670
| Temporary Service | 5/11/2006 | 5/15/2006 | 5/15/2006 10:18:38 AM | P | PASS |
|
|
###-#### - steve t/s u/g n ok
|
ELE06-01671
| Temporary Service | 5/11/2006 | 5/15/2006 | 5/15/2006 9:42:52 AM | A | PASS |
|
|
###-#### - steve t/s u/g n ok
|
ELE06-01672
| Temporary Service | 5/11/2006 | 5/15/2006 | 5/15/2006 9:42:13 AM | A | PASS |
|
|
###-#### - steve called contr, left survey, 210.53(G) the upper end of the electrode shall be flush with or below ground unless protected against physical damage , t/s u/g n ok
|
ELE03-04124
| Final | 5/12/2006 | 5/15/2006 | 5/15/2006 9:00:30 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/12/2006 at 2:25:28 PM. Contact: ###-####. corr made, ok to final
|
ELE06-01678
| Rough-In Permanent Service | 5/14/2006 | 5/15/2006 | 5/15/2006 8:27:04 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, left corr notice, nec 334.30 nm cable shall be stapled within 12" of enclosure, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) wall space over 6' shall have recpt, BCC all make-up shall be done,a/c disc set
|