Inspections for the day of: Monday, May 15, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00295 FIR-Aging Inspection5/15/20065/15/20065/18/2006 9:30:17 AM DONE
Telephone conversation with Gerald at Treasure Valley regarding the need to schedule inspection for the aging permits on this building ASAP.
FIR05-00759 INSP-Final Inspection5/12/20065/15/20065/16/2006 8:17:53 AMPDEFR
Inspection rescheduled per conversation with contractor.
FIR06-00298 INSP-Final Inspection5/12/20065/15/20065/16/2006 8:15:26 AMPPASS
Fire alarm work passed final inspection.
BLD06-00690 FIRE-Final Inspection5/12/20065/15/20065/16/2006 8:14:36 AMPPASS
Fire life safety is acceptable, related alarm work is complete, no sprinkler modifications required.
FIR05-00819 INSP-Sprinkler Rough-in/Hydro5/12/20065/15/20065/15/2006 1:11:47 PMAPART
Overhead hydrostatic test performed satisfactory. Need to provide correct spacing of pendent heads in the expanded office area, ESFR heads are blocked by ductwork at two locations, provide both high and intermediate temp heads in the head box.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro5/12/20065/15/20065/15/2006 11:36:49 AMAFAIL
One pendent head in a soffit at a south guest room is overspaced, missing a lateral EQ brace at the end of SW main, need to provide stamped plans showing field modifications at next inspection, all remaining areas on the 8th floor are acceptable for rough-in cover except as noted.