MIS06-00109
| FIR-Final | 5/12/2006 | 5/15/2006 | 5/19/2006 11:51:58 AM | A | PASS |
|
|
per bob, he left a correction notice stating that the church offices could be used for 90 days as long as the occupant load does not exceed 49 people.
|
BLD06-01107
| FIRE-Final Inspection | 5/15/2006 | 5/15/2006 | 5/15/2006 4:18:15 PM | P | PASS |
|
|
Life safety finaled
|
FIR05-00536
| INSP-Sprinkler Rough-in | 5/15/2006 | 5/15/2006 | 5/15/2006 4:12:11 PM | P | PART |
|
|
Inspection was for the basement of the new tower. Area inspected today was the west half of the basement. Some minor items have been found. See approved plans for locations.the east half of the system and all of the 6" standpiping needs inspected.
|
FIR06-00301
| INSP-Final Inspection | 5/12/2006 | 5/15/2006 | 5/15/2006 3:06:57 PM | P | PASS |
|
|
permit finaled.
|
MIS06-00111
| FIR-Final | 5/12/2006 | 5/15/2006 | 5/15/2006 1:49:51 PM | P | PART |
|
|
marcia; Phone #: ###-#### A temporary occupancy was given until: Remove or repair exit sign in the tenant space, remove thumbturn from the tenant exit. Keyed hardware on egress side with indicator is ok. Cover the exposed electrical outlets. Repair or replace the exit signs/emergency lights in the common corridor. Provide one additional fire extinguisher at the east end of the common corridor as discussed at no higher than 48" with a current inspection tag.
|
FIR06-00044
| FIR-Aging Inspection | 5/15/2006 | 5/15/2006 | 5/15/2006 1:20:53 PM | | NR |
|
|
Per Randy the work is done but they are waiting for the new control valve to be wired into the existing alarm system and will call in the inspection when that work is done.
|
MIS06-00110
| FIR-Final | 5/12/2006 | 5/15/2006 | 5/15/2006 10:44:06 AM | A | FAIL |
|
|
###-#### I called and let Jose know I was on the way to the job site. I could not find him of plans at the job site so I called him again to let him know I was there. He said he would be right there. I waited som more then left after leaving a correction notice stating that a suppression system is needed for the type 1 hodd and that plans are needed on the job site for inspection purposes
|
FIR06-00339
| INSP-Final Inspection | 5/11/2006 | 5/15/2006 | 5/15/2006 10:00:02 AM | A | PASS |
|
|
Permit finaled
|