| Electrical Rough-In | 5/15/2007 | 5/15/2007 | 5/15/2007 11:01:12 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/15/2007 at 7:01:10 AM. Contact: ###-####. called contr to move light boxes flush with finished surface, add couple nailplates, ric ok
|
ELE07-00570
| Electrical Rough-In | 5/14/2007 | 5/15/2007 | 5/15/2007 10:14:59 AM | A | PASS |
|
|
julian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, u/g ok house to garage
|
ELE07-01658
| Final | 5/14/2007 | 5/15/2007 | 5/15/2007 9:43:44 AM | A | PASS |
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
ELE07-01696
| Temporary Service | 5/14/2007 | 5/15/2007 | 5/15/2007 9:18:56 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe t/s u/g n ok
|
ELE05-01204
| Final | 5/11/2007 | 5/15/2007 | 5/15/2007 9:07:32 AM | A | PASS |
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made ok to final
|
ELE07-00794
| Rough-In Permanent Service | 5/14/2007 | 5/15/2007 | 5/15/2007 8:35:31 AM | A | FAIL |
|
|
jessie - ceiling ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met elect, told corr necessary are nec 330.30(B) mc cable shall be supported within 12" of terminations, 110.26(F)(1) drip protection for for foreign piping over panels,
|