ELE07-04192
| DOC - Permit Finaled | 5/15/2008 | 5/15/2008 | 5/15/2008 4:04:38 PM | P | PASS |
|
|
|
ELE08-01260
| Electrical Rough-In | 5/14/2008 | 5/15/2008 | 5/15/2008 3:41:21 PM | P | PASS |
|
|
jason Phone #: ###-####
|
ELE08-00795
| Final | 5/15/2008 | 5/15/2008 | 5/15/2008 3:05:27 PM | P | NH |
|
|
Please call Sam with Unico Properties if needed for final on new TI on south side of 12th floor. MPE not on site today, if needed call Joe at ###-####.Please feel free to chew out Joe at your discretion. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey called joe and gary and neather were there or knew what i was to do.
|
ELE07-00104
| DOC - Permit Expired | 5/15/2008 | 5/15/2008 | 5/15/2008 2:58:01 PM | P | PASS |
|
|
no work done in 11 mo.
|
ELE08-01226
| Electrical Rough-In | 5/15/2008 | 5/15/2008 | 5/15/2008 2:41:47 PM | P | FAIL |
|
|
Richard ###-#### or ###-#### inspector to sign Inspection Record Card!! pep remove insulation and uncover feed to garage protect romex as required 6 in. free conductor and box fill. insure that # 14 wire is connected to 15 a breaker.
|
ELE08-00795
| Electrical Rough-In | 5/15/2008 | 5/15/2008 | 5/15/2008 1:49:43 PM | P | NH |
|
|
Please call Gary for cieling inspection for cover on west side office area. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey Gary not on this job
|
ELE08-01046
| Electrical Rough-In | 5/15/2008 | 5/15/2008 | 5/15/2008 12:55:45 PM | P | NR |
|
|
steve Phone #: ###-#### both inspections on this permit should have been for the shell and core
|
ELE08-00510
| Final | 5/14/2008 | 5/15/2008 | 5/15/2008 10:43:49 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
|
ELE08-00100
| Electrical Rough-In | 5/14/2008 | 5/15/2008 | 5/15/2008 10:24:53 AM | A | FAIL |
|
|
Ceiling rough in inspection on phase 2 first floor. Phone #: ###-#### Internet Inspection Request from: Todd Sellman low voltage and flex shall not be on the grid. support all raceways properly. remove all box covers for grounding inspection and make up all grounds in each box according to 250.148. only 1 fixture is permitted to be fed from a fixture whip.
|
ELE08-00511
| Final | 5/14/2008 | 5/15/2008 | 5/15/2008 9:44:39 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
|
ELE08-01240
| Electrical Rough-In | 5/14/2008 | 5/15/2008 | 5/15/2008 9:16:33 AM | A | PART |
|
|
bonding & ug cover inspection, this is an existing pool, we are just doing electrical upgrade Phone #: ###-#### Internet Inspection Request from: Jari Rivers
u/g & bonding ok
|
ELE07-03585
| Electrical Rough-In | 5/14/2008 | 5/15/2008 | 5/15/2008 8:40:09 AM | A | PART |
|
|
cliff Note: ceiling grid Phone #: ###-#### grid ceilings on
|
ELE08-01151
| Electrical Rough-In | 5/14/2008 | 5/15/2008 | 5/15/2008 8:20:02 AM | P | CANC |
|
|
THIS IS A COVER UP INSPECTION. PLEASE CALL JIM 30 MIN. PRIOR TO INSPECTION @###-####. (IF POSSIBLE) Phone #: ###-#### Internet Inspection Request from: Shawna Gates Inspection cancelled from web by: Shawna Gates
|