Inspections for the day of: Thursday, May 15, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-04192 DOC - Permit Finaled5/15/20085/15/20085/15/2008 4:04:38 PMPPASS
ELE08-01260 Electrical Rough-In5/14/20085/15/20085/15/2008 3:41:21 PMPPASS
jason Phone #: ###-####
ELE08-00795 Final5/15/20085/15/20085/15/2008 3:05:27 PMPNH
Please call Sam with Unico Properties if needed for final on new TI on south side of 12th floor. MPE not on site today, if needed call Joe at ###-####.Please feel free to chew out Joe at your discretion. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey
called joe and gary and neather were there or knew what i was to do.
ELE07-00104 DOC - Permit Expired5/15/20085/15/20085/15/2008 2:58:01 PMPPASS
no work done in 11 mo.
ELE08-01226 Electrical Rough-In5/15/20085/15/20085/15/2008 2:41:47 PMPFAIL
Richard ###-#### or ###-#### inspector to sign Inspection Record Card!! pep
remove insulation and uncover feed to garage protect romex as required 6 in. free conductor and box fill. insure that # 14 wire is connected to 15 a breaker.
ELE08-00795 Electrical Rough-In5/15/20085/15/20085/15/2008 1:49:43 PMPNH
Please call Gary for cieling inspection for cover on west side office area. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey Gary not on this job
ELE08-01046 Electrical Rough-In5/15/20085/15/20085/15/2008 12:55:45 PMPNR
steve Phone #: ###-####
both inspections on this permit should have been for the shell and core
ELE08-00510 Final5/14/20085/15/20085/15/2008 10:43:49 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
ELE08-00100 Electrical Rough-In5/14/20085/15/20085/15/2008 10:24:53 AMAFAIL
Ceiling rough in inspection on phase 2 first floor. Phone #: ###-#### Internet Inspection Request from: Todd Sellman
low voltage and flex shall not be on the grid.
support all raceways properly.
remove all box covers for grounding inspection and make up all grounds in each box according to 250.148. only 1 fixture is permitted to be fed from a fixture whip.
ELE08-00511 Final5/14/20085/15/20085/15/2008 9:44:39 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
ELE08-01240 Electrical Rough-In5/14/20085/15/20085/15/2008 9:16:33 AMAPART
bonding & ug cover inspection, this is an existing pool, we are just doing electrical upgrade Phone #: ###-#### Internet Inspection Request from: Jari Rivers

u/g & bonding ok
ELE07-03585 Electrical Rough-In5/14/20085/15/20085/15/2008 8:40:09 AMAPART
cliff Note: ceiling grid Phone #: ###-####
grid ceilings on
ELE08-01151 Electrical Rough-In5/14/20085/15/20085/15/2008 8:20:02 AMPCANC
THIS IS A COVER UP INSPECTION. PLEASE CALL JIM 30 MIN. PRIOR TO INSPECTION @###-####. (IF POSSIBLE) Phone #: ###-#### Internet Inspection Request from: Shawna Gates Inspection cancelled from web by: Shawna Gates