FIR07-00946
| INSP-Conference | 5/15/2008 | 5/15/2008 | 5/15/2008 4:25:37 PM | P | DONE |
|
|
Regarding fire hat functionality at the elevator car.
|
FIR07-00663
| INSP-Sprinkler Rough-in | 5/15/2008 | 5/15/2008 | 5/15/2008 4:20:59 PM | P | PART |
|
|
Okay to cover underground supply line. Agreed to accept as-built plans for the deletion of the meter due to dedicated fire service.
|
BLD06-01451
| FIRE-Conference | 5/14/2008 | 5/15/2008 | 5/15/2008 4:18:39 PM | P | DONE |
|
|
On site discussion regarding FDC and pump test header locations.
|
FIR08-00240
| INSP-Final Inspection | 5/13/2008 | 5/15/2008 | 5/15/2008 4:15:27 PM | A | PART |
|
|
Relocate supply for one head piped below equipment obstructions per plan, attatch missing retaining strap at one main hanger-see plan annotations.
|
FIR07-00222
| INSP-Final Inspection | 5/13/2008 | 5/15/2008 | 5/15/2008 12:43:20 PM | A | PART |
|
|
Resubmittal plans match field install, need to attatch two missing retaining straps at beam clamps for arm over hangers at locations red-lined on plans prior to permit final.
|
BLD08-00370
| FIRE-Final Inspection | 5/14/2008 | 5/15/2008 | 5/15/2008 11:27:32 AM | A | PASS |
|
|
Fire life safety inspection completed satisfactory, noted plan modification to delete the phone room okay, doors at the exits to the common corridor deleted as QR sprinklers are in place.
|
FIR06-00595
| INSP-Alarm Testing | 5/15/2008 | 5/15/2008 | 5/15/2008 10:54:20 AM | A | PART |
|
|
Per contractor approved plan set indicates removal of existing spot type smoke detectors at the mechanical penthouse area-if installed spacing must meet code requirements, discussed schedule for next site visit 5/20.
|
BLD08-01013
| FIRE-Final Inspection | 5/14/2008 | 5/15/2008 | 5/15/2008 10:50:33 AM | A | PASS |
|
|
Corrections okayed, life safety passed.
|
BLD06-01994
| FIRE-Final Inspection | 5/14/2008 | 5/15/2008 | 5/15/2008 9:37:46 AM | A | FAIL |
|
|
Need approved plans and fire code review notes available on site, missing knox box, per contractor no fire extinguishers have been provided, lacking vehicle impact protection at the three new hydrants due to incomplete site work/curbing, will need access to each unit to test smoke alarms.
|
BLD06-01992
| FIRE-Final Inspection | 5/14/2008 | 5/15/2008 | 5/15/2008 9:36:57 AM | A | FAIL |
|
|
Need approved plans and fire code review notes available on site, missing knox box, per contractor no fire extinguishers have been provided, lacking vehicle impact protection at the three new hydrants due to incomplete site work/curbing, will need access to each unit to test smoke alarms.
|