Inspections for the day of: Thursday, May 15, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00946 INSP-Conference5/15/20085/15/20085/15/2008 4:25:37 PMPDONE
Regarding fire hat functionality at the elevator car.
FIR07-00663 INSP-Sprinkler Rough-in5/15/20085/15/20085/15/2008 4:20:59 PMPPART
Okay to cover underground supply line. Agreed to accept as-built plans for the deletion of the meter due to dedicated fire service.
BLD06-01451 FIRE-Conference5/14/20085/15/20085/15/2008 4:18:39 PMPDONE
On site discussion regarding FDC and pump test header locations.
FIR08-00240 INSP-Final Inspection5/13/20085/15/20085/15/2008 4:15:27 PMAPART
Relocate supply for one head piped below equipment obstructions per plan, attatch missing retaining strap at one main hanger-see plan annotations.
FIR07-00222 INSP-Final Inspection5/13/20085/15/20085/15/2008 12:43:20 PMAPART
Resubmittal plans match field install, need to attatch two missing retaining straps at beam clamps for arm over hangers at locations red-lined on plans prior to permit final.
BLD08-00370 FIRE-Final Inspection5/14/20085/15/20085/15/2008 11:27:32 AMAPASS
Fire life safety inspection completed satisfactory, noted plan modification to delete the phone room okay, doors at the exits to the common corridor deleted as QR sprinklers are in place.
FIR06-00595 INSP-Alarm Testing5/15/20085/15/20085/15/2008 10:54:20 AMAPART
Per contractor approved plan set indicates removal of existing spot type smoke detectors at the mechanical penthouse area-if installed spacing must meet code requirements, discussed schedule for next site visit 5/20.
BLD08-01013 FIRE-Final Inspection5/14/20085/15/20085/15/2008 10:50:33 AMAPASS
Corrections okayed, life safety passed.
BLD06-01994 FIRE-Final Inspection5/14/20085/15/20085/15/2008 9:37:46 AMAFAIL
Need approved plans and fire code review notes available on site, missing knox box, per contractor no fire extinguishers have been provided, lacking vehicle impact protection at the three new hydrants due to incomplete site work/curbing, will need access to each unit to test smoke alarms.
BLD06-01992 FIRE-Final Inspection5/14/20085/15/20085/15/2008 9:36:57 AMAFAIL
Need approved plans and fire code review notes available on site, missing knox box, per contractor no fire extinguishers have been provided, lacking vehicle impact protection at the three new hydrants due to incomplete site work/curbing, will need access to each unit to test smoke alarms.