ELE09-00525
| Electrical Rough-In | 5/14/2009 | 5/15/2009 | 5/15/2009 4:07:15 PM | P | CANC |
|
|
Dale ###-#### see added conf
|
ELE09-00525
| Conference | 5/15/2009 | 5/15/2009 | 5/15/2009 4:07:11 PM | P | DONE |
|
|
Dale ###-#### ok
|
ELE09-00238
| Final | 5/15/2009 | 5/15/2009 | 5/15/2009 3:35:55 PM | P | PASS |
|
|
Thanks for the clarification on the closet light. Phone #: ###-#### Internet Inspection Request from: Darryn ok
|
ELE08-02674
| Final | 5/14/2009 | 5/15/2009 | 5/15/2009 2:55:12 PM | A | PASS |
|
|
Please call Spencer McLean to meet at job site, ###-####. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean met with ele contr Mike K final ok
|
ELE09-00844
| Temporary Service | 5/15/2009 | 5/15/2009 | 5/15/2009 1:49:56 PM | P | FAIL |
|
|
Brandon Phone #: ###-#### called clean debri from t/s 200.2 (B) tie grded and grding together at t/s
|
ESC09-00132
| General Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 1:02:35 PM | P | PASS |
|
|
card posted site ok
|
ELE09-00820
| Electrical Rough-In | 5/15/2009 | 5/15/2009 | 5/15/2009 1:00:49 PM | P | PASS |
|
|
John- call 30 mins prior to going to meet Phone #: ###-#### pool bond and u/g ok
|
ELE07-02834
| Final | 5/14/2009 | 5/15/2009 | 5/15/2009 10:29:52 AM | A | FAIL |
|
|
Jared- call 30 mins prior to going for access Phone #: ###-#### see added r/i
|
ELE07-02834
| Electrical Rough-In | 5/15/2009 | 5/15/2009 | 5/15/2009 10:28:41 AM | A | FAIL |
|
|
Jared- call 30 mins prior to going for access Phone #: ###-#### hot tub wiring failed met contr, needs #6 manufactures instructions, u/g shall be 18 " deep
|
ESC09-00215
| General Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 9:51:46 AM | A | FAIL |
|
|
met rp needs hard surfaces clean or else he cleaning as we speak
|
ELE09-00795
| Electrical Rough-In | 5/14/2009 | 5/15/2009 | 5/15/2009 9:48:17 AM | A | PART |
|
|
Mike- trench cover inspection please Phone #: ###-#### west half u/g ok east half fail over 360 degrees of bends called
|
ELE09-00604
| Final | 5/14/2009 | 5/15/2009 | 5/15/2009 9:20:39 AM | A | FAIL |
|
|
Ron Phone #: ###-#### no access called
|
ESC09-00166
| General Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 8:35:48 AM | A | PASS |
|
|
ok
|
ELE09-00838
| Electrical Rough-In | 5/14/2009 | 5/15/2009 | 5/15/2009 8:34:49 AM | A | PASS |
|
|
work is in back yard. gate code is *2001 ready anytime, no rush Phone #: ###-#### Internet Inspection Request from: William Zerfas see failed r/i for p/s and subpanel, r/i ok for outside pario work
|
ELE09-00838
| Electrical Rough-In | 5/15/2009 | 5/15/2009 | 5/15/2009 8:33:55 AM | A | FAIL |
|
|
work is in back yard. gate code is *2001 ready anytime, no rush Phone #: ###-#### Internet Inspection Request from: William Zerfas corr called 110.26(F)(1&2) needs clearence for p/s and subpanel, note someone built cabinets in front of service panel
|
ESC09-00210
| General Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 7:47:27 AM | A | PART |
|
|
ok still needs hard surfaces swept
|
ELE09-00831
| Rough-In Permanent Service | 5/14/2009 | 5/15/2009 | 5/15/2009 7:46:02 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Stephen Kren r/i p/s u/g new ok
|