FIR08-00838
| INSP-Sprinkler Rough-in | 5/15/2009 | 5/15/2009 | 5/18/2009 12:42:53 PM | P | PART |
|
|
Overhead modifications are good for ceiling cover, be aware of possible obstructions to discharge that may develop due to proximity of light fixture junction boxes and pendent heads at some locations.
|
FIR08-00380
| INSP-Final Inspection | 5/15/2009 | 5/15/2009 | 5/18/2009 12:39:45 PM | P | NH |
|
|
Scheduled by a contractor via Hello! on 5/15/2009 at 10:20:38 AM. Contact: ###-####.
|
FIR09-00309
| INSP-Final Inspection | 5/15/2009 | 5/15/2009 | 5/18/2009 8:02:33 AM | P | NR |
|
|
Doug Phone #: ###-####
|
BLD09-00069
| FIRE-Final Inspection | 5/7/2009 | 5/15/2009 | 5/15/2009 2:41:43 PM | A | PASS |
|
|
One defficient location repaired while on site, inspection passed.
|
BLD08-02383
| FIRE-Final Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 2:35:25 PM | P | PASS |
|
|
Fire life safety finaled.
|
FIR09-00027
| INSP-Final Inspection | 5/14/2009 | 5/15/2009 | 5/15/2009 2:31:29 PM | A | PART |
|
|
UG fire supply line flush completed satisfactory.
|
FIR09-00182
| INSP-Final Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 1:38:10 PM | P | PASS |
|
|
Remaining two correction notice items completed, contractor to provide signals list and offsite account information for verification as discussed to PDS fire office.
|
BLD08-01992
| FIRE-Final Inspection | 5/14/2009 | 5/15/2009 | 5/15/2009 11:41:57 AM | A | FAIL |
|
|
Project is not ready for final fire life safety due to missing fire extinguishers, incompleted fire dept. access, missing building address, etc.
|
FIR08-00786
| INSP-Alarm Testing | 5/13/2009 | 5/15/2009 | 5/15/2009 11:39:02 AM | A | PART |
|
|
Testing completed for fire alarm notificaiton, initiation, and duct smoke detection for area "A" as marked on plan set. Still need record of inspection and testing forms and original stamped plan set, need to verify dB readings do not exceed max. allowed at the locker room and mechanical room entrys, provide correct descriptors matching sprinkler riser zones, verified account is set up, noted phone line troubles are not annunciated at the FACP-only indicated at the security panel.
|
FIR08-00157
| INSP-Final Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 9:21:12 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR05-00332
| INSP-Final Inspection | 5/14/2009 | 5/15/2009 | 5/15/2009 9:10:19 AM | A | PASS |
|
|
Fire sprinkler permit okay for final status.
|
FIR06-00297
| INSP-Final Inspection | 5/14/2009 | 5/15/2009 | 5/15/2009 12:00:00 AM | A | PASS |
|
|
Adam Phone #: ###-####
|
FIR09-00236
| INSP-Final Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/15/2009 at 6:44:02 AM. Contact: ###-####.
|
BLD08-02166
| FIRE-Final Inspection | 5/14/2009 | 5/15/2009 | 5/15/2009 12:00:00 AM | A | PASS |
|
|
rick Phone #: ###-####
|
FIR06-00167
| INSP-Final Inspection | 5/15/2009 | 5/15/2009 | 5/15/2009 12:00:00 AM | P | PASS |
|
|
Adam Phone #: ###-####
|