Inspections for the day of: Wednesday, May 15, 2013.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-03024 FIRE-Final Inspection5/15/20135/15/20135/15/2013 3:47:36 PMPPASS
Life safety passed
FIR13-00086 INSP-Sprinkler Rough-in5/14/20135/15/20135/15/2013 3:06:16 PMPCANC
Next phase is not ready for a final yet. I found overspaced audio/visual devices and in one location a device that is not wired up yet. Will be rescheduled.
BLD13-00021 FIRE-Final Inspection5/14/20135/15/20135/15/2013 2:54:20 PMACANC
Jeremy wants to reschedule for tomorrow - Phone #: ###-####
BLD13-00393 FIRE-Final Inspection5/15/20135/15/20135/15/2013 2:24:54 PMPPASS
Life safety passed. Owner is removing the locking hardware on the break room and replacing it with single action type.
BLD13-01193 FIRE-Final Inspection5/14/20135/15/20135/15/2013 11:16:45 AMAFAIL
Provide single action hardware and remove the thumbturn lock at the main exit.
FIR13-00037 INSP-Sprinkler Rough-in5/14/20135/15/20135/15/2013 9:57:14 AMAPASS
Rough to cover in basement and first floor for piping above the hardlids passed. See the city approved plans for exact locations.
BLD12-03024 FIRE-Final Inspection5/14/20135/15/20135/15/2013 9:06:52 AMAFAIL
Remove the double dead bolts from the door in the egress path and provide annual inspection for the fire extinguishers.