FIR14-00624
| INSP-Final Inspection | 5/15/2015 | 5/15/2015 | 5/15/2015 3:51:43 PM | P | FAIL |
|
|
Final passed and underground flush passed. Will be ok to final when the electric alarm bell has been relocated to the front of the house.
|
FIR14-00799
| INSP-Sprinkler Rough-in | 5/14/2015 | 5/15/2015 | 5/15/2015 3:49:55 PM | A | PART |
|
|
First floor rough-in passed. Need to address combustible concealed space at entrance. Hydro test failed. Second floor lobby area rough-in passed. Head in bottom of elevator shaft passed.
|
FIR15-00131
| INSP-Final Inspection | 5/15/2015 | 5/15/2015 | 5/15/2015 10:46:45 AM | P | PASS |
|
|
Permit finaled
|
BLD14-03543
| FIRE-Final Inspection | 5/14/2015 | 5/15/2015 | 5/15/2015 10:41:33 AM | A | PASS |
|
|
Life safety passed
|
BLD15-01138
| FIRE-Final Inspection | 5/15/2015 | 5/15/2015 | 5/15/2015 10:40:36 AM | P | FAIL |
|
|
Permit is required for hood suppression/appliance modification. Provide missing canopies for fire sprinklers. Provide teting of the smoke evac. system. Provide on 2A,10BC fire extinguisher with current inspection tag mounted in a normal path of travel. Remove the dead bolts from the front and rear doors. Provide single action hardware on the rear exit door. Provide city approved plans.
|
BLD15-01140
| FIRE-Final Inspection | 5/15/2015 | 5/15/2015 | 5/15/2015 10:34:08 AM | P | PASS |
|
|
Life safety passed
|
BLD15-01140
| FIRE-Final Inspection | 5/14/2015 | 5/15/2015 | 5/15/2015 9:50:02 AM | A | FAIL |
|
|
All items corrected except the smoke evac system is non-functional
|
FIR14-00759
| INSP-Sprinkler Rough-in/Hydro | 5/14/2015 | 5/15/2015 | 5/15/2015 7:39:45 AM | A | PASS |
|
|
Rough-in passed. Piping can not be covered until a tenting inspection has passed.
|
BLD15-01138
| FIRE-Final Inspection | 5/14/2015 | 5/15/2015 | 5/15/2015 12:00:00 AM | A | CANC |
|
|