Inspections for the day of: Friday, May 15, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01623 Electrical Rough-In5/14/20205/15/20205/15/2020 2:04:40 PMPPASS
lock box code 1776 contact Caleb with any questions or concerns. Phone #: ###-#### Inspection requested via web by Caleb Gaylord Only kitchen walls open, rest only re-fed existing locations. Rough in ok cover.
ELE20-01675 Final5/15/20205/15/20205/15/2020 1:31:25 PMPFAIL
Please call 1 hour before inspection Phone #: ###-#### Inspection requested via web by Calvin Bohrer
210.63- A receptacle outlet shall be installed with in 25' of new AC unit.
422.30- A disconnecting means shall be provided for new furnace.
ELE20-01660 Final5/14/20205/15/20205/15/2020 12:41:54 PMAPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan Final ok
ELE20-01660 Electrical Rough-In5/15/20205/15/20205/15/2020 12:41:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan
All surface mounted to disconnecting means from existing exterior source. Rough in ok.
ELE20-00508 Final5/15/20205/15/20205/15/2020 10:50:25 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
ELE20-01671 Rough-In Permanent Service5/14/20205/15/20205/15/2020 9:45:06 AMAPASS
Phone #: ###-#### Inspection requested via web by ron spen cer
Rough in ok cover p/s o/h n ok
ELE20-01663 Electrical Rough-In5/14/20205/15/20205/15/2020 9:14:36 AMAPASS
Ufer inspection Please inspect at 8:00AM if possible. Call Mike at number listed for site location. Phone #: ###-#### Inspection requested via web by Tye Thomas
Partial pour, 1/0 installed with future stubs to ground ring. Rough in oik cover