Inspections for the day of: Friday, May 15, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01604 Rough-In Permanent Service5/11/20205/15/20205/15/2020 1:19:05 PMPPASS
please call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon...
p/s u/g relocation ok
ELE20-01681 Final5/15/20205/15/20205/15/2020 12:37:38 PMPCANC
Install is complete to the disconnect. Tub is being delivered this morning and I will be onsite at 11 to complete wiring. Should be complete by 1-2pm Phone #: ###-#### Inspection requested via web by Sean Patton...
service change required before final can be given...50A circuit overload existing 100A service panel
ELE20-01681 Electrical Rough-In5/15/20205/15/20205/15/2020 12:36:37 PMPPASS
Install is complete to the disconnect. Tub is being delivered this morning and I will be onsite at 11 to complete wiring. Should be complete by 1-2pm Phone #: ###-#### Inspection requested via web by Sean Patton...

wiring from panel thru attic to disconnect other side of house...romex to thhn in emt...50A GFCI breaker in disconnect
requiring a service change before permit can be finaled....hot tub circuit will overload 100A service
ELE20-00982 Final5/14/20205/15/20205/15/2020 11:28:13 AMAPASS
Phone #: ###-#### Inspection requested via web by Rodney Monroe...ok to final
ELE20-01625 Final5/14/20205/15/20205/15/2020 9:48:35 AMAPASS
They will be home. Robyn ; Frank - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks...disconnect moved so not behind A/C...ok to final
ELE20-01664 Temporary Service5/14/20205/15/20205/15/2020 8:20:40 AMAPASS
Please call the electrician Matt ###-#### one hour before arriving at the job site to meet him there. Thanks. Phone #: ###-#### Inspection requested via web by Nicholas Buck...
t/s u/g new ok