Inspections for the day of: Friday, May 15, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00050 INSP-Final Inspection5/12/20205/15/20205/15/2020 4:02:14 PMPPASS
Final fire sprinkler inspection for scope of work is complete.

Please call 30 minutes prior to arrival so we can make sure we can get in Phone #: ###-#### Inspection requested via web by Sam Ball
FIR20-00318 INSP-Sprinkler Rough-in5/15/20205/15/20205/15/2020 11:14:18 AMPPASS
Protective coating has been applied to restraint rods, all underground supply line approved for cover.
FIR20-00201 INSP-Sprinkler Rough-in5/14/20205/15/20205/15/2020 11:12:54 AMAPASS
Rough to cover inspection for areas of work completed via photos, per photos area of work is approved for cover.

Don Forester Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR20-00181 INSP-Final Inspection5/13/20205/15/20205/15/2020 9:20:29 AMAPASS
Final fire alarm inspection for area of work is complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR20-00270 INSP-Final Inspection5/13/20205/15/20205/15/2020 9:20:05 AMAPASS
Final fire alarm inspection for area of work is complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR20-00318 INSP-Sprinkler Rough-in5/14/20205/15/20205/15/2020 9:19:38 AMAPART
Rough to cover inspection for exterior underground piping complete, approved for cover. Plans need to updated showing C900 pipe for riser instead of IBR. Restraint rods need protective coating applied to whole sections of restraint rods, during inspection only about 1/3 of restraint rods had protective coating applied, point of contact was sent message about protective coating but as of this entry no response has been received. Exterior pipe is approved for cover, interior riser cannot be covered until protective coating has been applied and verified.

Exterior 2nd half of the rough in on the under ground to cover. Please call Chris Ford. Phone #: ###-#### Inspection requested via web by Jessia McLain
FIR20-00214 INSP-Final Inspection5/14/20205/15/20205/15/2020 9:15:28 AMAPASS
Final fire sprinkler inspection for area of work is complete.

Screened- Don Phone #: ###-####
FIR20-00214 INSP-Sprinkler Rough-in5/14/20205/15/20205/15/2020 9:14:54 AMAPASS
Rough to cover inspection for area of work is complete, approved for cover.

Screened- Don Phone #: ###-####