Inspections for the day of: Friday, May 16, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-00964 Final5/14/20035/16/20035/16/2003 12:00:00 AMAFAIL
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted met with contractor, no violations to be retained,110.3(B) use only manufactors listed breakers, 300.11 shall not use grid to support raceways, 314.19, and 20 boxes shall be flush with combustible material, 110.12(A) seal breaker KOs 5/16/2003 10:22:08 AM
ELE03-01423 Final5/15/20035/16/20035/16/2003 12:00:00 AMAPASS
###-#### dennis tench ok final ok 5/16/2003 11:14:19 AM
ELE03-01427 Rough-In Permanent Service5/15/20035/16/20035/16/2003 12:00:00 AMAPASS
###-#### r/i ok
p/s u/g new ok 5/16/2003 9:11:09 AM
ELE03-01413 Electrical Rough-In5/16/20035/16/20035/16/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 5/16/2003 at 7:51:20 AM. Contact: ###-####. r/i ok back of garage made into family rm 5/16/2003 3:03:12 PM
ELE03-00888 Final5/16/20035/16/20035/16/2003 12:00:00 AMPPASS
###-#### Jimmy ok 5/16/2003 3:47:06 PM
ELE03-01391 Electrical Rough-In5/16/20035/16/20035/16/2003 12:00:00 AMPPART
Contact Chris Carmine - rough in signs; Phone #: ###-#### Internet Inspection Request from: Deb McCoy r/i ok flex for signs 5/16/2003 3:03:42 PM
ELE02-01004 Final5/16/20035/16/20035/16/2003 12:00:00 AMPPASS
ok
ELE02-01016 Final5/16/20035/16/20035/16/2003 12:00:00 AMPPASS
ok
ELE02-01017 Final5/16/20035/16/20035/16/2003 12:00:00 AMPPASS
ok
ELE02-01018 Final5/16/20035/16/20035/16/2003 12:00:00 AMPPASS
ok
ELE02-01019 Final5/16/20035/16/20035/16/2003 12:00:00 AMPPASS
ok