FIR04-00161
| INSP-Final Inspection | 5/13/2005 | 5/16/2005 | 5/16/2005 2:46:19 PM | P | FAIL |
|
|
Two upright heads in vault are spaced too far off wall to meet OH 1 requirements for this space. Provide map at riser indicating location of auxillary drains. Provide test certificates. Verify foreward flow through BFP as required by note #59. Provide sp
|
BLD05-00517
| FIRE-Final Inspection | 5/16/2005 | 5/16/2005 | 5/16/2005 12:14:35 PM | P | PASS |
|
|
Fire life safety finaled.
|