BLD04-02637
| FIRE-Final Inspection | 5/16/2005 | 5/16/2005 | 5/16/2005 4:27:09 PM | P | FAIL |
|
|
Remove thumbturns from exit doors, provide approved hardware on the pocket door, provide missing hardware for verification, mount fire extinguishers, provide revised floor plan for suite 100 to building dept. plan review
|
BLD04-01882
| FIRE-Conference | 5/16/2005 | 5/16/2005 | 5/16/2005 4:16:12 PM | P | DONE |
|
|
I spoke to the general contractor about requirements for a fire alarm system. The plan review comments were missing several pages but it appears it is not a requirement in the sheets that I looked at.
|
FIR05-00222
| INSP-Sprinkler Rough-in | 5/13/2005 | 5/16/2005 | 5/16/2005 4:11:56 PM | P | PASS |
|
|
Underground supply line is ok to cover with bedding. Needs inspection before final cover.
|
FIR04-00768
| INSP-Alarm Testing | 5/13/2005 | 5/16/2005 | 5/16/2005 3:42:19 PM | A | FAIL |
|
|
Provide signal verification and nfpa 72 record of completion forms.
|
FIR05-00164
| INSP-Final Inspection | 5/13/2005 | 5/16/2005 | 5/16/2005 1:16:45 PM | A | PASS |
|
|
Suppression system operated correctly
|
BLD03-03009
| FIRE-Final Inspection | 5/13/2005 | 5/16/2005 | 5/16/2005 9:01:03 AM | A | PASS |
|
|
fire life safety finaled
|