Inspections for the day of: Monday, May 16, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02637 FIRE-Final Inspection5/16/20055/16/20055/16/2005 4:27:09 PMPFAIL
Remove thumbturns from exit doors, provide approved hardware on the pocket door, provide missing hardware for verification, mount fire extinguishers, provide revised floor plan for suite 100 to building dept. plan review
BLD04-01882 FIRE-Conference5/16/20055/16/20055/16/2005 4:16:12 PMPDONE
I spoke to the general contractor about requirements for a fire alarm system. The plan review comments were missing several pages but it appears it is not a requirement in the sheets that I looked at.
FIR05-00222 INSP-Sprinkler Rough-in5/13/20055/16/20055/16/2005 4:11:56 PMPPASS
Underground supply line is ok to cover with bedding. Needs inspection before final cover.
FIR04-00768 INSP-Alarm Testing5/13/20055/16/20055/16/2005 3:42:19 PMAFAIL
Provide signal verification and nfpa 72 record of completion forms.
FIR05-00164 INSP-Final Inspection5/13/20055/16/20055/16/2005 1:16:45 PMAPASS
Suppression system operated correctly
BLD03-03009 FIRE-Final Inspection5/13/20055/16/20055/16/2005 9:01:03 AMAPASS
fire life safety finaled