Inspections for the day of: Tuesday, May 16, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01709 Permanent Service5/16/20065/16/20065/16/2006 3:14:53 PMPFAIL
inspection on 200amp service, any questions call andy @###-#### Internet Inspection Request from: Andy Rose corr called 250.56 grd rods shall be 6ft apart, 230.54(C) service drop shall be below wheatherhead
ELE06-01235 Final5/16/20065/16/20065/16/2006 2:46:43 PMPPASS
don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
ELE06-01683 Electrical Rough-In5/15/20065/16/20065/16/2006 2:20:56 PMPPASS
larry -re-insp on uffer ground; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for dirt cover
ELE05-03320 Final5/12/20065/16/20065/16/2006 1:48:20 PMPCANC
Scheduled by a contractor via Hello! on 5/12/2006 at 3:33:11 PM. Contact: ###-####. talked to contractor and owner will do inspection 05-17-06 am
ELE06-00464 Electrical Rough-In5/16/20065/16/20065/16/2006 1:22:06 PMPPART
Scheduled by a contractor via Hello! on 5/16/2006 at 9:39:48 AM. Contact: ###-####. all shell, core wiring except still needs inspection for all panel feeders for tenant spaces
ELE06-00464 Permanent Service5/16/20065/16/20065/16/2006 1:20:49 PMPPASS
Scheduled by a contractor via Hello! on 5/16/2006 at 9:39:48 AM. Contact: ###-####. p/s u/g new ok for house panel meter
ELE06-01633 Electrical Rough-In5/15/20065/16/20065/16/2006 12:16:34 PMAPART
laura; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls hard ceilings ok
ELE06-00214 Final5/15/20065/16/20065/16/2006 10:48:03 AMAFAIL
Scheduled by a contractor via Hello! on 5/15/2006 at 6:35:28 PM. Contact: ###-####. corr. called shall provide manufactures access for j tub motor and recepts, install all closet shelves and rods, outlet right of fireplace no power, outside paddle fan is it listed for outside
ELE06-01717 Temporary Service5/15/20065/16/20065/16/2006 10:04:26 AMAPASS
HZ ###-#### t/s u/g new ok
ELE06-01727 Electrical Rough-In5/15/20065/16/20065/16/2006 9:51:05 AMAPART
wet niche--all american elec ###-####
potting and u/g , bond ok still needs equipotential grid inspection called
ELE06-01654 Permanent Service5/15/20065/16/20065/16/2006 9:23:50 AMAFAIL
###-#### - celica winters corr. called 250.28 where is the bond screw?, 250.66&28(D) shall use #4 copper too all bond bushings for line side, 408.3(E) high leg shall be B phase
ELE05-04583 Final5/15/20065/16/20065/16/2006 8:43:23 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire ok
ELE05-04581 Final5/15/20065/16/20065/16/2006 8:42:49 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire ok