ELE06-01709
| Permanent Service | 5/16/2006 | 5/16/2006 | 5/16/2006 3:14:53 PM | P | FAIL |
|
|
inspection on 200amp service, any questions call andy @###-#### Internet Inspection Request from: Andy Rose corr called 250.56 grd rods shall be 6ft apart, 230.54(C) service drop shall be below wheatherhead
|
ELE06-01235
| Final | 5/16/2006 | 5/16/2006 | 5/16/2006 2:46:43 PM | P | PASS |
|
|
don; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
|
ELE06-01683
| Electrical Rough-In | 5/15/2006 | 5/16/2006 | 5/16/2006 2:20:56 PM | P | PASS |
|
|
larry -re-insp on uffer ground; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for dirt cover
|
ELE05-03320
| Final | 5/12/2006 | 5/16/2006 | 5/16/2006 1:48:20 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 5/12/2006 at 3:33:11 PM. Contact: ###-####. talked to contractor and owner will do inspection 05-17-06 am
|
ELE06-00464
| Electrical Rough-In | 5/16/2006 | 5/16/2006 | 5/16/2006 1:22:06 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 5/16/2006 at 9:39:48 AM. Contact: ###-####. all shell, core wiring except still needs inspection for all panel feeders for tenant spaces
|
ELE06-00464
| Permanent Service | 5/16/2006 | 5/16/2006 | 5/16/2006 1:20:49 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/16/2006 at 9:39:48 AM. Contact: ###-####. p/s u/g new ok for house panel meter
|
ELE06-01633
| Electrical Rough-In | 5/15/2006 | 5/16/2006 | 5/16/2006 12:16:34 PM | A | PART |
|
|
laura; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls hard ceilings ok
|
ELE06-00214
| Final | 5/15/2006 | 5/16/2006 | 5/16/2006 10:48:03 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/15/2006 at 6:35:28 PM. Contact: ###-####. corr. called shall provide manufactures access for j tub motor and recepts, install all closet shelves and rods, outlet right of fireplace no power, outside paddle fan is it listed for outside
|
ELE06-01717
| Temporary Service | 5/15/2006 | 5/16/2006 | 5/16/2006 10:04:26 AM | A | PASS |
|
|
HZ ###-#### t/s u/g new ok
|
ELE06-01727
| Electrical Rough-In | 5/15/2006 | 5/16/2006 | 5/16/2006 9:51:05 AM | A | PART |
|
|
wet niche--all american elec ###-#### potting and u/g , bond ok still needs equipotential grid inspection called
|
ELE06-01654
| Permanent Service | 5/15/2006 | 5/16/2006 | 5/16/2006 9:23:50 AM | A | FAIL |
|
|
###-#### - celica winters corr. called 250.28 where is the bond screw?, 250.66&28(D) shall use #4 copper too all bond bushings for line side, 408.3(E) high leg shall be B phase
|
ELE05-04583
| Final | 5/15/2006 | 5/16/2006 | 5/16/2006 8:43:23 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire ok
|
ELE05-04581
| Final | 5/15/2006 | 5/16/2006 | 5/16/2006 8:42:49 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire ok
|