FIR05-00402
| FIR-Aging Inspection | 5/16/2006 | 5/16/2006 | 5/17/2006 1:42:10 PM | | DONE |
|
|
The building is currently still under construction, work in progress.
|
BLD05-03235
| FIRE-Final Inspection | 5/16/2006 | 5/16/2006 | 5/17/2006 8:05:25 AM | P | NR |
|
|
The project related hood suppression permit must be finaled before final life safety inspection.
|
FIR05-00759
| INSP-Final Inspection | 5/16/2006 | 5/16/2006 | 5/16/2006 3:28:56 PM | P | FAIL |
|
|
Installation does not match plan-cd rating and floor plan do not reflect field conditions. Horns and strobes on both 1st and 2nd floors are not in sync as required.
|
FIR06-00234
| INSP-Final Inspection | 5/15/2006 | 5/16/2006 | 5/16/2006 2:46:07 PM | A | PASS |
|
|
Fire sprinkler work is satisfactory. Note: one head has been changed from a SW as indicated on plans to a pendent due to Hanel construction.
|
FIR06-00202
| INSP-Final Inspection | 5/10/2006 | 5/16/2006 | 5/16/2006 1:41:33 PM | A | PASS |
|
|
Fire sprinkler inspection passed, permit finaled.
|
FIR06-00150
| INSP-Final Inspection | 5/10/2006 | 5/16/2006 | 5/16/2006 12:20:19 PM | A | PASS |
|
|
Fire sprinkler work is acceptable, inspection passed.
|
FIR06-00201
| INSP-Final Inspection | 5/15/2006 | 5/16/2006 | 5/16/2006 12:17:34 PM | A | PASS |
|
|
Fire alarm inspection is satisfactory, permit finaled.
|
FIR06-00184
| INSP-Final Inspection | 5/10/2006 | 5/16/2006 | 5/16/2006 12:16:37 PM | A | PASS |
|
|
Fire alarm work passed final field inspection.
|
FIR05-00459
| INSP-Final Inspection | 5/15/2006 | 5/16/2006 | 5/16/2006 10:38:09 AM | A | FAIL |
|
|
Spot checked EOL locations do not match plans.
|