FIR05-00822
| INSP-Sprinkler Rough-in/Hydro | 5/16/2007 | 5/16/2007 | 5/16/2007 4:05:54 PM | P | DEFR |
|
|
Inspection rescheduled.
|
BLD06-01790
| FIRE-Final Inspection | 5/16/2007 | 5/16/2007 | 5/16/2007 4:05:28 PM | P | PASS |
|
|
Inspection passed.
|
BLD06-02862
| FIRE-Final Inspection | 5/16/2007 | 5/16/2007 | 5/16/2007 4:04:56 PM | P | PASS |
|
|
Life safety inspection passed, noted missing door hardware to be installed prior to structural final.
|
FIR07-00341
| INSP-Sprinkler Rough-in/Hydro | 5/15/2007 | 5/16/2007 | 5/16/2007 4:03:18 PM | A | FAIL |
|
|
Hood system does not appear to be interconnected with the building FA system, need to provide class K PFE with current tag, one appliance needs to be raised to within 4' of the hood lip.
|
FIR06-00901
| FIR-Aging Inspection | 5/16/2007 | 5/16/2007 | 5/16/2007 2:28:23 PM | | DONE |
|
|
wip
|
FIR07-00230
| INSP-Sprinkler Rough-in | 5/16/2007 | 5/16/2007 | 5/16/2007 2:21:40 PM | P | PART |
|
|
UG supply line to the point extended to the street is approved for bury.
|
FIR07-00198
| INSP-Final Inspection | 5/15/2007 | 5/16/2007 | 5/16/2007 1:38:03 PM | A | NR |
|
|
Pending project related fire alarm permit work.
|
FIR06-01002
| INSP-Final Inspection | 5/15/2007 | 5/16/2007 | 5/16/2007 1:30:31 PM | A | NR |
|
|
Final pending testing of the riser supervision, also need to verifiy items noted at the previous inspection completed on 5/4-see activities under permit FIR06-00939- including missing coverage above the drop ceilings north of the kitchen area, one SSU is blocked at a storage room by a roof access hatch, missing hanger at one east branch line, no approved plans were on site as required.
|
FIR06-00939
| INSP-Final Inspection | 5/15/2007 | 5/16/2007 | 5/16/2007 1:24:16 PM | A | PASS |
|
|
Permit for the UG fire supply line portion of this project finaled.
|
FIR06-00800
| INSP-Sprinkler Rough-in/Hydro | 5/15/2007 | 5/16/2007 | 5/16/2007 1:18:03 PM | P | NR |
|
|
Not ready for inspection per conversation with contractor.
|
MIS07-00043
| FIR-Final | 5/15/2007 | 5/16/2007 | 5/16/2007 1:08:05 PM | A | FAIL |
|
|
Need to provide current certification tags for the fire extinguishers, post max. occupant load sign per permit notes, provide signage at the main entry/exit door.
|
FIR07-00372
| INSP-Sprinkler Rough-in | 5/15/2007 | 5/16/2007 | 5/16/2007 12:38:34 PM | A | PART |
|
|
UG fire supply line is approved for cover, provide method for seismic clearance at the floor slab, need to verifiy which road box controls the east suply line as it was not apparent.
|
FIR07-00371
| INSP-Sprinkler Rough-in | 5/15/2007 | 5/16/2007 | 5/16/2007 12:35:24 PM | A | PART |
|
|
UG fire supply line okay for cover, noted the need for seismic clearance at the floor slab.
|
MIS07-00110
| FIR-Final | 5/15/2007 | 5/16/2007 | 5/16/2007 12:04:48 PM | A | PASS |
|
|
Life safety inspection passed, noted lever hardware at the mens restroom to be installed prior to structural final as discussed.
|
BLD06-01095
| FIRE-Final Inspection | 5/15/2007 | 5/16/2007 | 5/16/2007 11:40:13 AM | A | FAIL |
|
|
Need to provide a current annual inspection for the existing fire sprinkler system, remove manual thumbturn at the back exit door from the warehouse area, mount PFE at the front office area, storage must be a min. of 18" below sprinklers, one PFE on the 2nd floor is overdue annual certification.
|
FIR05-00536
| INSP-Sprinkler Rough-in/Hydro | 5/15/2007 | 5/16/2007 | 5/16/2007 11:33:27 AM | A | PART |
|
|
Hydrostatic testing for the NW standpipe completed satisfactory, also approved for cover the 2nd floor mezzanine and 1st floor lobby grid ceiling areas as red lined and initialed on stamped plans.
|
FIR07-00130
| INSP-Sprinkler Rough-in | 5/15/2007 | 5/16/2007 | 5/16/2007 10:27:06 AM | A | FAIL |
|
|
Need approved plan resubmittals prior to approval for cover at the attic dry system.
|
FIR07-00130
| INSP-Sprinkler Rough-in/Hydro | 5/15/2007 | 5/16/2007 | 5/16/2007 10:24:58 AM | A | CANC |
|
|
Pending plan resubmittals.
|
FIR06-00728
| INSP-Final Inspection | 5/9/2007 | 5/16/2007 | 5/14/2007 3:25:45 PM | A | CANC |
|
|
Mike Bierman is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR06-00704
| INSP-Final Inspection | 5/14/2007 | 5/16/2007 | 5/14/2007 2:00:42 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|