Inspections for the day of: Wednesday, May 16, 2007.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00822 INSP-Sprinkler Rough-in/Hydro5/16/20075/16/20075/16/2007 4:05:54 PMPDEFR
Inspection rescheduled.
BLD06-01790 FIRE-Final Inspection5/16/20075/16/20075/16/2007 4:05:28 PMPPASS
Inspection passed.
BLD06-02862 FIRE-Final Inspection5/16/20075/16/20075/16/2007 4:04:56 PMPPASS
Life safety inspection passed, noted missing door hardware to be installed prior to structural final.
FIR07-00341 INSP-Sprinkler Rough-in/Hydro5/15/20075/16/20075/16/2007 4:03:18 PMAFAIL
Hood system does not appear to be interconnected with the building FA system, need to provide class K PFE with current tag, one appliance needs to be raised to within 4' of the hood lip.
FIR06-00901 FIR-Aging Inspection5/16/20075/16/20075/16/2007 2:28:23 PM DONE
wip
FIR07-00230 INSP-Sprinkler Rough-in5/16/20075/16/20075/16/2007 2:21:40 PMPPART
UG supply line to the point extended to the street is approved for bury.
FIR07-00198 INSP-Final Inspection5/15/20075/16/20075/16/2007 1:38:03 PMANR
Pending project related fire alarm permit work.
FIR06-01002 INSP-Final Inspection5/15/20075/16/20075/16/2007 1:30:31 PMANR
Final pending testing of the riser supervision, also need to verifiy items noted at the previous inspection completed on 5/4-see activities under permit FIR06-00939- including missing coverage above the drop ceilings north of the kitchen area, one SSU is blocked at a storage room by a roof access hatch, missing hanger at one east branch line, no approved plans were on site as required.
FIR06-00939 INSP-Final Inspection5/15/20075/16/20075/16/2007 1:24:16 PMAPASS
Permit for the UG fire supply line portion of this project finaled.
FIR06-00800 INSP-Sprinkler Rough-in/Hydro5/15/20075/16/20075/16/2007 1:18:03 PMPNR
Not ready for inspection per conversation with contractor.
MIS07-00043 FIR-Final5/15/20075/16/20075/16/2007 1:08:05 PMAFAIL
Need to provide current certification tags for the fire extinguishers, post max. occupant load sign per permit notes, provide signage at the main entry/exit door.
FIR07-00372 INSP-Sprinkler Rough-in5/15/20075/16/20075/16/2007 12:38:34 PMAPART
UG fire supply line is approved for cover, provide method for seismic clearance at the floor slab, need to verifiy which road box controls the east suply line as it was not apparent.
FIR07-00371 INSP-Sprinkler Rough-in5/15/20075/16/20075/16/2007 12:35:24 PMAPART
UG fire supply line okay for cover, noted the need for seismic clearance at the floor slab.
MIS07-00110 FIR-Final5/15/20075/16/20075/16/2007 12:04:48 PMAPASS
Life safety inspection passed, noted lever hardware at the mens restroom to be installed prior to structural final as discussed.
BLD06-01095 FIRE-Final Inspection5/15/20075/16/20075/16/2007 11:40:13 AMAFAIL
Need to provide a current annual inspection for the existing fire sprinkler system, remove manual thumbturn at the back exit door from the warehouse area, mount PFE at the front office area, storage must be a min. of 18" below sprinklers, one PFE on the 2nd floor is overdue annual certification.
FIR05-00536 INSP-Sprinkler Rough-in/Hydro5/15/20075/16/20075/16/2007 11:33:27 AMAPART
Hydrostatic testing for the NW standpipe completed satisfactory, also approved for cover the 2nd floor mezzanine and 1st floor lobby grid ceiling areas as red lined and initialed on stamped plans.
FIR07-00130 INSP-Sprinkler Rough-in5/15/20075/16/20075/16/2007 10:27:06 AMAFAIL
Need approved plan resubmittals prior to approval for cover at the attic dry system.
FIR07-00130 INSP-Sprinkler Rough-in/Hydro5/15/20075/16/20075/16/2007 10:24:58 AMACANC
Pending plan resubmittals.
FIR06-00728 INSP-Final Inspection5/9/20075/16/20075/14/2007 3:25:45 PMACANC
Mike Bierman is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
FIR06-00704 INSP-Final Inspection5/14/20075/16/20075/14/2007 2:00:42 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley