Inspections for the day of: Friday, May 16, 2008.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03110 Final5/16/20085/16/20085/16/2008 4:09:08 PMPPASS
called contractor regard status, he says he is done with job. ok to final
ELE07-01873 Final5/16/20085/16/20085/16/2008 4:04:44 PMPPASS
Thomas Phone #: ###-#### met owner, ok to final
ESC07-01314 General Inspection5/16/20085/16/20085/16/2008 3:57:59 PMPPASS
still under construction, looked ok
ESC08-00155 General Inspection5/16/20085/16/20085/16/2008 3:55:21 PMPPASS
sign up, no activity yet, looked ok
ESC07-00404 Site Preparation5/16/20085/16/20085/16/2008 3:53:46 PMPPASS
dirt in driveway for landscaping they are moving, looked ok
ESC08-00302 General Inspection5/16/20085/16/20085/16/2008 3:50:29 PMAPASS
looked ok
ESC08-00113 General Inspection5/16/20085/16/20085/16/2008 3:49:23 PMPPASS
sign up, looked ok
ESC08-00164 General Inspection5/16/20085/16/20085/16/2008 3:46:00 PMAPASS
looked ok
ESC07-00071 General Inspection5/16/20085/16/20085/16/2008 3:40:00 PMAPASS
grounds look ok
ELE08-01273 Electrical Rough-In5/16/20085/16/20085/16/2008 3:38:24 PMPPASS
diane Phone #: ###-#### ric ok
ELE08-01284 Electrical Rough-In5/16/20085/16/20085/16/2008 3:24:57 PMPPASS
randy Note: please inspect late afternoon - call 1/2 hr prior to inspection Phone #: ###-#### ric ok
ELE08-01283 Electrical Rough-In5/16/20085/16/20085/16/2008 2:45:05 PMPPASS
Andrew; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok
ELE08-00804 Permanent Service5/16/20085/16/20085/16/2008 2:20:24 PMPPASS
in need of inspection on service grounding Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange p/s u/g n ok
ELE08-01265 Temporary Service5/15/20085/16/20085/16/2008 1:29:02 PMPPASS
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS t/s o/h n ok
ELE08-01278 Rough-In Permanent Service5/15/20085/16/20085/16/2008 12:54:33 PMAFAIL
unfished basement, thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable called, left correction notice, NEC 334.30 nm cable shall be secured within 12" of box, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 110.12 (C) there shall be no damaged equipment-jacket of ser cable, 334.80 shall derate conductors where more than 2 nm cables pass thru framing that is to be fire or draft stopped, 334.30 shall secure nm cable within 12" of box, 210.52(A)(1)&(2) receptacles shall be spaced such that no point along wall line is over 6' from a receptacle, 210.8(A)(5) shall provide gfci in basement
ELE08-01228 Electrical Rough-In5/15/20085/16/20085/16/2008 10:59:44 AMAPASS
steve Phone #: ###-#### ric ok
ELE08-01092 Electrical Rough-In5/15/20085/16/20085/16/2008 10:53:00 AMAPASS
This is a swimming pool. Please inspect the equipotenial grid.
Thanks Phone #: ###-#### Internet Inspection Request from: Chris Weimar equipotential grid ok to pour
ELE08-01274 Rough-In Permanent Service5/15/20085/16/20085/16/2008 10:43:39 AMAFAIL
bicandi ele Phone #: ###-#### called, left correction notice, NEC 250.52(A)(1) shall ground to metal water pipe witjin 5' of entering building with #4, 352.30(A) shall secure rnc within 3' of panel, 334.30 nm shall be secured within 12" of panel, 210.52(A)(2) wall space over 2' shall have receptacles installed- kitchen north walls
ELE07-02451 Final5/15/20085/16/20085/16/2008 10:07:30 AMAPART
Partial Final. Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson left correction notice BCC shall complete kitchen, ice melt system west entry ceiling (ri), NEC shall rigidly mount outside receptacles per 314 and 406.4, cord corrected in ceilings, anop, signed t/o card
ELE08-00745 Electrical Rough-In5/15/20085/16/20085/16/2008 9:27:22 AMAPASS
tom Note: potting compound on nitch lights for pools Phone #: ###-#### called to check on equipotential grid, potting only ok
ELE08-01229 Electrical Rough-In5/15/20085/16/20085/16/2008 8:42:51 AMAPASS
steve Phone #: ###-#### ric ok
ELE08-00998 Electrical Rough-In5/15/20085/16/20085/16/2008 8:14:47 AMAPASS
added diving board and ladder. need additional bonding inspection Phone #: ###-#### Internet Inspection Request from: joe wheeler bond ok for ladder, cover,diving board
ELE08-01273 Electrical Rough-In5/15/20085/16/20085/16/2008 7:45:40 AMANH
craig Phone #: ###-#### called, left sticker