ELE07-03110
| Final | 5/16/2008 | 5/16/2008 | 5/16/2008 4:09:08 PM | P | PASS |
|
|
called contractor regard status, he says he is done with job. ok to final
|
ELE07-01873
| Final | 5/16/2008 | 5/16/2008 | 5/16/2008 4:04:44 PM | P | PASS |
|
|
Thomas Phone #: ###-#### met owner, ok to final
|
ESC07-01314
| General Inspection | 5/16/2008 | 5/16/2008 | 5/16/2008 3:57:59 PM | P | PASS |
|
|
still under construction, looked ok
|
ESC08-00155
| General Inspection | 5/16/2008 | 5/16/2008 | 5/16/2008 3:55:21 PM | P | PASS |
|
|
sign up, no activity yet, looked ok
|
ESC07-00404
| Site Preparation | 5/16/2008 | 5/16/2008 | 5/16/2008 3:53:46 PM | P | PASS |
|
|
dirt in driveway for landscaping they are moving, looked ok
|
ESC08-00302
| General Inspection | 5/16/2008 | 5/16/2008 | 5/16/2008 3:50:29 PM | A | PASS |
|
|
looked ok
|
ESC08-00113
| General Inspection | 5/16/2008 | 5/16/2008 | 5/16/2008 3:49:23 PM | P | PASS |
|
|
sign up, looked ok
|
ESC08-00164
| General Inspection | 5/16/2008 | 5/16/2008 | 5/16/2008 3:46:00 PM | A | PASS |
|
|
looked ok
|
ESC07-00071
| General Inspection | 5/16/2008 | 5/16/2008 | 5/16/2008 3:40:00 PM | A | PASS |
|
|
grounds look ok
|
ELE08-01273
| Electrical Rough-In | 5/16/2008 | 5/16/2008 | 5/16/2008 3:38:24 PM | P | PASS |
|
|
diane Phone #: ###-#### ric ok
|
ELE08-01284
| Electrical Rough-In | 5/16/2008 | 5/16/2008 | 5/16/2008 3:24:57 PM | P | PASS |
|
|
randy Note: please inspect late afternoon - call 1/2 hr prior to inspection Phone #: ###-#### ric ok
|
ELE08-01283
| Electrical Rough-In | 5/16/2008 | 5/16/2008 | 5/16/2008 2:45:05 PM | P | PASS |
|
|
Andrew; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok
|
ELE08-00804
| Permanent Service | 5/16/2008 | 5/16/2008 | 5/16/2008 2:20:24 PM | P | PASS |
|
|
in need of inspection on service grounding Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange p/s u/g n ok
|
ELE08-01265
| Temporary Service | 5/15/2008 | 5/16/2008 | 5/16/2008 1:29:02 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS t/s o/h n ok
|
ELE08-01278
| Rough-In Permanent Service | 5/15/2008 | 5/16/2008 | 5/16/2008 12:54:33 PM | A | FAIL |
|
|
unfished basement, thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable called, left correction notice, NEC 334.30 nm cable shall be secured within 12" of box, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 110.12 (C) there shall be no damaged equipment-jacket of ser cable, 334.80 shall derate conductors where more than 2 nm cables pass thru framing that is to be fire or draft stopped, 334.30 shall secure nm cable within 12" of box, 210.52(A)(1)&(2) receptacles shall be spaced such that no point along wall line is over 6' from a receptacle, 210.8(A)(5) shall provide gfci in basement
|
ELE08-01228
| Electrical Rough-In | 5/15/2008 | 5/16/2008 | 5/16/2008 10:59:44 AM | A | PASS |
|
|
steve Phone #: ###-#### ric ok
|
ELE08-01092
| Electrical Rough-In | 5/15/2008 | 5/16/2008 | 5/16/2008 10:53:00 AM | A | PASS |
|
|
This is a swimming pool. Please inspect the equipotenial grid. Thanks Phone #: ###-#### Internet Inspection Request from: Chris Weimar equipotential grid ok to pour
|
ELE08-01274
| Rough-In Permanent Service | 5/15/2008 | 5/16/2008 | 5/16/2008 10:43:39 AM | A | FAIL |
|
|
bicandi ele Phone #: ###-#### called, left correction notice, NEC 250.52(A)(1) shall ground to metal water pipe witjin 5' of entering building with #4, 352.30(A) shall secure rnc within 3' of panel, 334.30 nm shall be secured within 12" of panel, 210.52(A)(2) wall space over 2' shall have receptacles installed- kitchen north walls
|
ELE07-02451
| Final | 5/15/2008 | 5/16/2008 | 5/16/2008 10:07:30 AM | A | PART |
|
|
Partial Final. Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson left correction notice BCC shall complete kitchen, ice melt system west entry ceiling (ri), NEC shall rigidly mount outside receptacles per 314 and 406.4, cord corrected in ceilings, anop, signed t/o card
|
ELE08-00745
| Electrical Rough-In | 5/15/2008 | 5/16/2008 | 5/16/2008 9:27:22 AM | A | PASS |
|
|
tom Note: potting compound on nitch lights for pools Phone #: ###-#### called to check on equipotential grid, potting only ok
|
ELE08-01229
| Electrical Rough-In | 5/15/2008 | 5/16/2008 | 5/16/2008 8:42:51 AM | A | PASS |
|
|
steve Phone #: ###-#### ric ok
|
ELE08-00998
| Electrical Rough-In | 5/15/2008 | 5/16/2008 | 5/16/2008 8:14:47 AM | A | PASS |
|
|
added diving board and ladder. need additional bonding inspection Phone #: ###-#### Internet Inspection Request from: joe wheeler bond ok for ladder, cover,diving board
|
ELE08-01273
| Electrical Rough-In | 5/15/2008 | 5/16/2008 | 5/16/2008 7:45:40 AM | A | NH |
|
|
craig Phone #: ###-#### called, left sticker
|