Inspections for the day of: Wednesday, May 16, 2012.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00621 FIR-Aging Inspection5/16/20125/16/20125/24/2012 10:11:05 AM NR
Work is in progress
BLD12-01177 FIRE-Final Inspection5/16/20125/16/20125/17/2012 7:06:11 AMPFAIL
Need to remove or repair the exit sign. Provide testing of the mall engineered smoke evac system.
BLD11-02834 BLD-Conference5/15/20125/16/20125/16/2012 3:40:23 PMADONE
The general contractor, the owner Steven Wong and I discussed sprinkler spacing issues. I deferred him to a qualified sprinkler contractor to perform a walk through to address potential obstruction issues. We also discussed fire alarm notification device placement and hood suppression system interconnections. I also went over new exit sign/emergency light placement and door hardware requirements.
BLD11-01066 FIRE-Final Inspection5/16/20125/16/20125/16/2012 2:41:09 PMPPASS
Life safety passed.
BLD12-00727 FIRE-Final Inspection5/15/20125/16/20125/16/2012 11:56:00 AMAPASS
Life safety passed
BLD11-01066 FIRE-Final Inspection5/15/20125/16/20125/16/2012 10:18:12 AMAFAIL
Repair the one non functional emergency light, provide certification for two fire extinguishers and provide verification that the wall between the Green Room and the Stage, with doors #4 and #8 are not now required to be fire rated. I left a message with Dan in plan review requesting clarification. A re-inspection has been scheduled for this afternoon.
FIR10-00577 INSP-Final Inspection5/11/20125/16/20125/16/2012 9:44:20 AMAFAIL
I went ahead and tested the horn/strobe and the smoke detectors for the door release. The devices functioned correctly and the signals received at the central station. The smoke detectors have been centered at the doors. What is not complete are the plans. Per the original correction notice plans needed to be re-submitted or as-builts provided showing the 30cd strobe. The fire alarm vendor chose to re-submit for a plan modification. The problem is the plan modifications show a 110cd strobe where the 30cd has been installed. Also the room size is incorrect and the actual location of the work is in the south end of the building not as shown in the north end of the building. As discussed an accurate as-built package needs to be provided prior to a final sign off.