Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01463 Conference5/15/20175/16/20175/16/2017 1:33:13 PMPDONE
Please call ahead for access - Ivan Phone #: ###-#### Talked about "class 6 " pole for perm power pole.Tamper/ weather resistant receps for temp power. GFCI protection. Grounding of service.
ELE17-00419 Final5/15/20175/16/20175/16/2017 12:26:21 PMPFAIL
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine 210.8 A 3 All Outdoor receps shall be GFCI Protected. ( All W/P on house) 334.15 Exposed NM Cable shall be protected from physical damage. ( Under kitchen sink connecting D/W) 210.52 A 2 1 Wall space 2ft or greater shall have recep. ( Bed #2 under light switch)
ELE17-01187 Final5/16/20175/16/20175/16/2017 11:37:45 AMPPASS
Barry is the contact Phone #: ###-#### Inspection requested via web by Thaniel Bishop final ok
ELE17-01187 Electrical Rough-In5/16/20175/16/20175/16/2017 11:37:14 AMPPASS
Barry is the contact Phone #: ###-#### Inspection requested via web by Thaniel Bishop solar rough in ok
ELE14-02192 Final5/15/20175/16/20175/16/2017 10:57:04 AMPPASS
Phone #: ###-#### Inspection requested via web by Thomas wilson final ok
ELE16-02744 Electrical Rough-In5/15/20175/16/20175/16/2017 9:19:27 AMAPASS
Am if possible. Just bathroom cielings in lower clubhouse level. Thanks. Phone #: ###-#### Inspection requested via web by Harley Woodward Bathrooms only Ceiling only ok to cover
ELE17-01452 Electrical Rough-In5/16/20175/16/20175/16/2017 9:00:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Jason Wicks corrections made Walls only ok to cover