Inspections for the day of: Tuesday, May 16, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00284 INSP-Sprinkler Rough-in5/15/20175/16/20175/16/2017 2:33:02 PMACANC
Duplicate inspection
FIR16-00284 INSP-Sprinkler Rough-in5/15/20175/16/20175/16/2017 2:32:42 PMAPASS
1st and 3rd floor south side corridor soffit heads are ok to cover. I noted one area on both the first and third floors where sprinkler pendants are less than 8' apart which is not allowed for extended coverage heads. I need verification that the heads can be that close or heads need to be relocated.
FIR16-00738 INSP-Sprinkler Rough-in/Hydro5/16/20175/16/20175/16/2017 1:07:02 PMPPASS
Wet system hydro test passed. Also the sprinkler heads that have been added to the combustible concealed spaces above the fire places are ok to cover.
BLD17-00238 FIRE-Final Inspection5/16/20175/16/20175/16/2017 1:01:04 PMPPASS
life safety passed
BLD17-01478 FIRE-Final Inspection5/15/20175/16/20175/16/2017 9:10:11 AMAPASS
Life safety passed
FIR17-00051 INSP-Final Inspection5/15/20175/16/20175/16/2017 7:17:05 AMAPASS
Final fire alarm inspection passed/complete