FIR16-00284
| INSP-Sprinkler Rough-in | 5/15/2017 | 5/16/2017 | 5/16/2017 2:33:02 PM | A | CANC |
|
|
Duplicate inspection
|
FIR16-00284
| INSP-Sprinkler Rough-in | 5/15/2017 | 5/16/2017 | 5/16/2017 2:32:42 PM | A | PASS |
|
|
1st and 3rd floor south side corridor soffit heads are ok to cover. I noted one area on both the first and third floors where sprinkler pendants are less than 8' apart which is not allowed for extended coverage heads. I need verification that the heads can be that close or heads need to be relocated.
|
FIR16-00738
| INSP-Sprinkler Rough-in/Hydro | 5/16/2017 | 5/16/2017 | 5/16/2017 1:07:02 PM | P | PASS |
|
|
Wet system hydro test passed. Also the sprinkler heads that have been added to the combustible concealed spaces above the fire places are ok to cover.
|
BLD17-00238
| FIRE-Final Inspection | 5/16/2017 | 5/16/2017 | 5/16/2017 1:01:04 PM | P | PASS |
|
|
life safety passed
|
BLD17-01478
| FIRE-Final Inspection | 5/15/2017 | 5/16/2017 | 5/16/2017 9:10:11 AM | A | PASS |
|
|
Life safety passed
|
FIR17-00051
| INSP-Final Inspection | 5/15/2017 | 5/16/2017 | 5/16/2017 7:17:05 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|