Inspections for the day of: Thursday, May 17, 2001.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-01592 Temporary Service5/16/20015/17/20015/17/2001 12:00:00 AMAFAIL
###-#### cor. posted called left message seal ko , install bond screw, 220 v outlet needs cover use G E breakers only remove sq D breakers 5/17/2001 10:38:46 AM
ELE01-00969 Electrical Rough-In5/16/20015/17/20015/17/2001 12:00:00 AMAPART
underground Martin ###-#### pager u/g r/i and conference ok 5/17/2001 11:48:16 AM
ELE01-01595 Final5/16/20015/17/20015/17/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 05/16/2001 at 14:29:08. Contact: ###-####. ok 5/17/2001 1:07:08 PM
ELE01-01420 Final5/16/20015/17/20015/17/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 05/16/2001 at 14:36:37. Contact: ###-####. ok 5/17/2001 1:06:58 PM
ELE01-00113 Final5/16/20015/17/20015/17/2001 12:00:00 AMAPASS
Andy ###-#### ok 5/17/2001 4:52:23 PM
ELE01-00121 Final5/17/20015/17/20015/17/2001 12:00:00 AMPFAIL
Tyler ###-#### cor. posted called 110-26 provide clearence in front, and top of panel 110-3(b) remove wire and in manufactures breaker tie bar, 384-13 label panel 5/17/2001 1:44:57 PM
ELE01-01612 Temporary Service5/17/20015/17/20015/17/2001 12:00:00 AMPFAIL
tom ###-#### cor. posted called left message clean t/s gray wire not allowed for use as ungrounded conductor 12 ft clearence over driveway 5/17/2001 2:23:37 PM
ELE01-01575 Electrical Rough-In5/17/20015/17/20015/17/2001 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 05/17/2001 at 10:41:17. Contact: . walls and u/g 5/17/2001 4:52:55 PM
ELE01-01400 Electrical Rough-In5/15/20015/17/20015/17/2001 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 05/15/2001 at 07:51:30. Contact: ###-####. walls ok 5/16/2001 8:52:26 AM