Inspections for the day of: Tuesday, May 17, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00222 INSP-Sprinkler Rough-in5/17/20055/17/20055/17/2005 4:11:02 PMPPASS
Underground supply piping is ok to cover
FIR05-00217 INSP-Supply line flush5/17/20055/17/20055/17/2005 3:45:55 PMPPASS
Underground supply line flush and underground hydro test passed. I had contractor measure leakage. 5 1/2 quarts was allowed and it lost approx. 2 1/2 to 3 quarts
MIS05-00056 FIR-Final5/17/20055/17/20055/17/2005 1:48:56 PMPPART
A temporary occupancy was given until sprinkler coverage is provided in the walkin cooler, the fire extinguisher is lowered and provided with a current inspection tag and the menu sign is relocated as discussed so that it will not block sprinkler coverage
FIR05-00217 INSP-Sprinkler Rough-in5/17/20055/17/20055/17/2005 12:04:57 PMPFAIL
I started rough-in inspection on the dry system at the request of the onsite sprinkler fitter but could not do the inspection due to pipe routing and sizing not matching approved plans. Upright heads are not spaced in accordance with NFPA 13 for obstruct
BLD04-02121 FIRE-Conference5/16/20055/17/20055/17/2005 11:14:15 AMADONE
Spoke to Phil about duct smoke detector locations. The north one needs relocated to be ahead of the elbow
BLD04-01267 FIRE-Final Inspection5/16/20055/17/20055/17/2005 9:23:47 AMAPART
A temporary occupancy was given with Sam Rogers permission. Items needing correcting are adding exit discharge lighting outside of the main exit, adding emergency lighting in the main lobby and in the south conference room, and adding a exit sign at the b
FIR04-00768 INSP-Final Inspection5/16/20055/17/20055/17/2005 9:21:05 AMAPASS
Fire alarm finaled