Inspections for the day of: Wednesday, May 17, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00559 ELE-Aging Inspection5/17/20065/17/20065/19/2006 11:55:47 AM NR
suc
ELE06-01700 Electrical Rough-In5/17/20065/17/20065/17/2006 4:08:59 PMPPASS
Scheduled by a contractor via Hello! on 5/17/2006 at 7:21:46 AM. Contact: ###-####.
\R/I Ok
ELE06-00299 Conference5/17/20065/17/20065/17/2006 3:37:49 PMPPART
ken - call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
talked about recep placement and make-up
ELE06-01240 Final5/17/20065/17/20065/17/2006 3:13:17 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ELE06-00511 Electrical Rough-In5/17/20065/17/20065/17/2006 3:03:37 PMPPART
this is for an underground if you have any questions please call Chris Hill; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
U/G ok
ELE06-00247 Electrical Rough-In5/17/20065/17/20065/17/2006 2:47:12 PMPPART
STEVE NOTE; PARTIAL COVER; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
lights on front of building ok
ELE06-01729 Electrical Rough-In5/17/20065/17/20065/17/2006 2:22:24 PMPPART
BOB; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
underground to garage ok
ELE06-01729 Permanent Service5/17/20065/17/20065/17/2006 2:21:33 PMPFAIL
BOB; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
no clearance in front of main panel and meter.
only 1 ground rod.
overfused edison based fuses.
connect to water within 5 ft and range and dryer 4 wires.
ELE06-01757 Temporary Service5/17/20065/17/20065/17/2006 1:04:35 PMPPASS
###-#### bernice
T/S U/G Ok
ELE06-01709 Permanent Service5/16/20065/17/20065/17/2006 10:31:52 AMAFAIL
re inspection on service. any questions call Andy @ ###-#### Internet Inspection Request from: Andy Rose
drop over alley not high enough
ELE06-01546 Electrical Rough-In5/16/20065/17/20065/17/2006 10:03:54 AMANR
Scheduled by a contractor via Hello! on 5/16/2006 at 3:29:25 PM. Contact: ###-####.
this is not a code electric job
ELE06-00851 Final5/16/20065/17/20065/17/2006 9:48:23 AMAPASS
FINAL INSPECTION PLEASE @ MONGOLIAN GRILL; Phone #: ###-#### Internet Inspection Request from: Barry Kendall
ELE06-00511 Electrical Rough-In5/16/20065/17/20065/17/2006 8:55:20 AMANR
this is for an underground inspection, any questions please call Chris Hill; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
ELE05-04007 Conference5/17/20065/17/20065/17/2006 8:40:31 AMAPART
Phone #: ###-#### Internet Inspection Request from: Jim Williams
discussed location of outlets