FIR05-00201
| FIR-Aging Inspection | 5/17/2006 | 5/17/2006 | 5/18/2006 9:28:28 AM | | DONE |
|
|
Spoke with Gerald at Treasure Valley to schedule inspection for the aging permits on this building ASAP.
|
BLD04-02303
| FIRE-Final Inspection | 5/16/2006 | 5/17/2006 | 5/18/2006 7:31:01 AM | P | PASS |
|
|
Items on previous correction notice have been completed, inspection passed.
|
FIR05-00787
| INSP-Supply line flush | 5/16/2006 | 5/17/2006 | 5/17/2006 2:06:18 PM | A | PART |
|
|
UG fire supply lines are good for cover, will need to provide means for seismic clearance where the riser pipe passes through the floor slab, pipe is required to be bedded before backfill.
|
FIR06-00282
| INSP-Sprinkler Rough-in/Hydro | 5/16/2006 | 5/17/2006 | 5/17/2006 1:41:09 PM | A | PART |
|
|
Inspection was for overhead rough-in cover. The installation matches plans which are currently being resubmitted per contractor. Rough-in as installed is okay pending city plan review approval. Three areas as marked on plans need corrected including overspacing at a corridor intersection, head too close to a wall in SW room, the elevator shaft head needs to be QR.
|
BLD05-03235
| FIRE-Final Inspection | 5/16/2006 | 5/17/2006 | 5/17/2006 11:36:35 AM | A | FAIL |
|
|
The project related hood inspection has failed, also need to remove the manual thumbturn at the main entry/exit door, repair non-functional exit sign and discharge light at the west exit, provide max. occupant load sign as indicated on review notes, need to provide means to test HVAC duct SD devices at next inspection, not all life safety items reviewed at this time.
|
FIR06-00333
| INSP-Final Inspection | 5/16/2006 | 5/17/2006 | 5/17/2006 11:32:40 AM | A | FAIL |
|
|
Need to provide K class extinguisher, provide proper separation between the fryer and wok burner, provide signage at the manual pulls designating to which hood the pull activates.
|