Inspections for the day of: Thursday, May 17, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00501 INSP-Final Inspection5/16/20075/17/20075/18/2007 12:55:30 PMAPASS
permit finaled
FIR06-00978 INSP-Final Inspection5/16/20075/17/20075/18/2007 9:15:38 AMPFAIL
The plans have not been resubmitted as previously requested. no inspection performed
FIR07-00306 INSP-Final Inspection5/17/20075/17/20075/17/2007 5:37:21 PMPPASS
Permit finaled
FIR07-00433 INSP-Sprinkler Rough-in5/16/20075/17/20075/17/2007 3:21:35 PMPPASS
Sprinkler piping is ok to cover.
FIR07-00198 INSP-Final Inspection5/17/20075/17/20075/17/2007 3:20:06 PMPPASS
Hood suppression system operated correctly per Mike Timmerman. Permit finaled.
FIR07-00159 INSP-Final Inspection5/16/20075/17/20075/17/2007 3:18:45 PMAPASS
Permit finaled and performed by Mike Timmerman
FIR06-00755 INSP-Sprinkler Rough-in5/16/20075/17/20075/17/2007 10:56:36 AMAPASS
underground cover inspection passed
MIS07-00043 FIR-Final5/16/20075/17/20075/17/2007 10:42:23 AMAPASS
life safety passed. scott performed the inspection
BLD07-00665 FIRE-Final Inspection5/16/20075/17/20075/17/2007 10:13:29 AMAFAIL
This project was not ready for inspection but I went over some of the required items with the owner. Fire sprinkler heads are overspaced. Fire extinguishers need to be installed. There are no appliances under the kitchen hood yet so the suppression system needs recertified and tested. Door hardware is not installed. Exit signs and emergency lights will need to be tested.
FIR05-00822 INSP-Sprinkler Rough-in/Hydro5/16/20075/17/20075/17/2007 9:59:33 AMAFAIL
The overhead hydro was started but is now failed because the riser room door is locked and nobody seems to be able to find a key.
FIR07-00225 INSP-Sprinkler Rough-in5/16/20075/17/20075/17/2007 9:04:28 AMAPART
Sprinkler piping is ok to cover but one additional pendant is needed on the second floor against the east wall. This will be verified at the final.
BLD07-00181 FIRE-Final Inspection5/16/20075/17/20075/17/2007 8:10:07 AMAPASS
life safety passed
FIR07-00231 INSP-Final Inspection5/17/20075/17/20075/17/2007 8:09:42 AMPPASS
permit finaled