FIR11-00174
| INSP-Final Inspection | 5/17/2011 | 5/17/2011 | 5/17/2011 5:25:50 PM | P | PART |
|
|
Need to complete hydrostatic test per NFPA 25 component replacement action table, heads at the meat prep and bloom room have not been replaced, pendent heads at the seafood area are degraded.
|
FIR11-00108
| INSP-Final Inspection | 5/17/2011 | 5/17/2011 | 5/17/2011 5:21:16 PM | P | PASS |
|
|
Verified resubmital plans, final inspection passed.
|
FIR11-00202
| INSP-Sprinkler Rough-in | 5/16/2011 | 5/17/2011 | 5/17/2011 5:19:56 PM | A | PART |
|
|
Overhead rough-in passed inspection- one additional head to be installed at under stairway storage room, noted field mods at branch line routing okayed. Cover approval pending satisfactory tenting and insulation inspection prior to sheetrock.
|
BLD11-00299
| FIRE-Final Inspection | 5/16/2011 | 5/17/2011 | 5/17/2011 5:14:09 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR11-00119
| INSP-Final Inspection | 5/16/2011 | 5/17/2011 | 5/17/2011 5:13:34 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|