BLD12-01094
| FIRE-Final Inspection | 5/17/2012 | 5/17/2012 | 5/17/2012 3:48:22 PM | P | PASS |
|
|
life safety passed
|
FIR12-00175
| INSP-Sprinkler Rough-in/Hydro | 5/16/2012 | 5/17/2012 | 5/17/2012 3:36:23 PM | P | PASS |
|
|
The overhead hydro test passed. The sprinkler piping in the Sanctuary/Fellowship areas is ok to cover.
|
FIR12-00230
| INSP-Sprinkler Rough-in | 5/17/2012 | 5/17/2012 | 5/17/2012 3:06:47 PM | P | PASS |
|
|
Sprinkler piping can be covered.
|
FIR12-00135
| INSP-Final Inspection | 5/16/2012 | 5/17/2012 | 5/17/2012 3:04:29 PM | P | FAIL |
|
|
The light fixtures have not been installed yet and may cause obstructions. Also the blow-in insulation has not been installed over the piping. Insulation should be done monday so Ken will call for final for tuesday.
|
BLD12-01177
| FIRE-Final Inspection | 5/17/2012 | 5/17/2012 | 5/17/2012 2:43:22 PM | P | PASS |
|
|
Life safety passed. The smoke evac system functioned correctly.
|
BLD12-00850
| FIRE-Final Inspection | 5/16/2012 | 5/17/2012 | 5/17/2012 11:36:11 AM | A | PART |
|
|
Per Romeo Gervais a temporary occupancy is approved until the obstructions around the notification devices has been removed. A annual inspection report has been received by the fire dept from Allied General.
|
FIR12-00236
| INSP-Sprinkler Rough-in | 5/16/2012 | 5/17/2012 | 5/17/2012 11:18:32 AM | A | PASS |
|
|
Sprinkler piping is ok to cover.
|
BLD12-00322
| FIRE-Final Inspection | 5/16/2012 | 5/17/2012 | 5/17/2012 11:16:30 AM | A | FAIL |
|
|
Provide annual inspection for the fire extinguishers. Provide sticker at the main exit as discussed. Remove the dead bolts from the doors and provide single action hardware as discussed.
|
FIR10-00577
| INSP-Final Inspection | 5/16/2012 | 5/17/2012 | 5/17/2012 11:15:00 AM | A | PASS |
|
|
Permit finaled
|
FIR12-00133
| INSP-Sprinkler Rough-in | 5/16/2012 | 5/17/2012 | 5/17/2012 11:03:59 AM | A | CANC |
|
|
Cancel per bruce. Insulation is not yet complete will call for re-inspection next week.
|
BLD12-00870
| FIRE-Final Inspection | 5/16/2012 | 5/17/2012 | 5/17/2012 9:46:57 AM | A | PASS |
|
|
life safety passed
|
BLD12-01111
| FIRE-Final Inspection | 5/16/2012 | 5/17/2012 | 5/17/2012 9:46:31 AM | A | PASS |
|
|
Life safety passed. Owner is removing the thumb turn on both front exit doors and providing keyed on the main exit and single action hardware on the second exit.
|
FIR12-00130
| INSP-Final Inspection | 5/14/2012 | 5/17/2012 | 5/17/2012 12:00:00 AM | A | FAIL |
|
|
Smoke detector and manual pull station have been installed. Netcon was at an acceptable level of 5, all signals reported to central station. However, the alarm signals (pull station and water flow) did not intiate an audible alarm at the panel (required by NFPA 72 10.7). The smoke detector was not tested.
|