Inspections for the day of: Friday, May 17, 2013.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00895 FIRE-Final Inspection5/16/20135/17/20135/17/2013 5:24:05 PMAPEND
Pending fire alarm questions
FIR13-00197 INSP-Final Inspection5/15/20135/17/20135/17/2013 5:18:03 PMAFAIL
Correction notice items include; provide WP notification appliances at rooms 118 and 119, MP at the riser needs to be between 42" and 48" AFF per note #33, new wall at hall 111 will require additional coverage, remove existing A/V at the fire riser room, post accurate points map at the panel per note # 51, post signage per note #53, relay for sound system shutdown did not function. Plan modification needed due to six existing duct detectors and one hood monitor not included on approved plans. Revise matrix to include sound relay. Revise one-line diagram to include all building duct detectors and initiating devices.
BLD13-00075 FIRE-Final Inspection5/17/20135/17/20135/17/2013 1:28:35 PMPPASS
C/N items finished. Manual thumbturn at the back warehouse area exit door to be removed prior to structural final as discussed.
FIR13-00174 INSP-Final Inspection5/15/20135/17/20135/17/2013 1:26:58 PMAPASS
Scope of work complete, site inspection passed. Fire alarm permit finaled.
FIR13-00173 INSP-Final Inspection5/15/20135/17/20135/17/2013 1:24:34 PMAPASS
Scope of fire alarm work passed field inspection. Permit finaled.
FIR13-00172 INSP-Final Inspection5/15/20135/17/20135/17/2013 1:19:58 PMAPASS
Scope of fire alarm work completed, permit finaled.
FIR13-00158 INSP-Final Inspection5/16/20135/17/20135/17/2013 10:56:27 AMAPASS
Fire sprinkler work passed field inspection. Permit okay for final.
FIR13-00183 INSP-Final Inspection5/16/20135/17/20135/17/2013 10:54:56 AMAPASS
Scope of fire sprinkler work completed and passed final inspection.
FIR13-00068 INSP-Final Inspection5/16/20135/17/20135/17/2013 10:53:33 AMANR
Mark J is the contact Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus * Plans currently in "review" status.
FIR13-00068 INSP-Sprinkler Rough-in5/16/20135/17/20135/17/2013 10:52:00 AMANR
Mark J is the contact Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus * Plans currently in "review" status.