BLD13-00895
| FIRE-Final Inspection | 5/16/2013 | 5/17/2013 | 5/17/2013 5:24:05 PM | A | PEND |
|
|
Pending fire alarm questions
|
FIR13-00197
| INSP-Final Inspection | 5/15/2013 | 5/17/2013 | 5/17/2013 5:18:03 PM | A | FAIL |
|
|
Correction notice items include; provide WP notification appliances at rooms 118 and 119, MP at the riser needs to be between 42" and 48" AFF per note #33, new wall at hall 111 will require additional coverage, remove existing A/V at the fire riser room, post accurate points map at the panel per note # 51, post signage per note #53, relay for sound system shutdown did not function. Plan modification needed due to six existing duct detectors and one hood monitor not included on approved plans. Revise matrix to include sound relay. Revise one-line diagram to include all building duct detectors and initiating devices.
|
BLD13-00075
| FIRE-Final Inspection | 5/17/2013 | 5/17/2013 | 5/17/2013 1:28:35 PM | P | PASS |
|
|
C/N items finished. Manual thumbturn at the back warehouse area exit door to be removed prior to structural final as discussed.
|
FIR13-00174
| INSP-Final Inspection | 5/15/2013 | 5/17/2013 | 5/17/2013 1:26:58 PM | A | PASS |
|
|
Scope of work complete, site inspection passed. Fire alarm permit finaled.
|
FIR13-00173
| INSP-Final Inspection | 5/15/2013 | 5/17/2013 | 5/17/2013 1:24:34 PM | A | PASS |
|
|
Scope of fire alarm work passed field inspection. Permit finaled.
|
FIR13-00172
| INSP-Final Inspection | 5/15/2013 | 5/17/2013 | 5/17/2013 1:19:58 PM | A | PASS |
|
|
Scope of fire alarm work completed, permit finaled.
|
FIR13-00158
| INSP-Final Inspection | 5/16/2013 | 5/17/2013 | 5/17/2013 10:56:27 AM | A | PASS |
|
|
Fire sprinkler work passed field inspection. Permit okay for final.
|
FIR13-00183
| INSP-Final Inspection | 5/16/2013 | 5/17/2013 | 5/17/2013 10:54:56 AM | A | PASS |
|
|
Scope of fire sprinkler work completed and passed final inspection.
|
FIR13-00068
| INSP-Final Inspection | 5/16/2013 | 5/17/2013 | 5/17/2013 10:53:33 AM | A | NR |
|
|
Mark J is the contact Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus * Plans currently in "review" status.
|
FIR13-00068
| INSP-Sprinkler Rough-in | 5/16/2013 | 5/17/2013 | 5/17/2013 10:52:00 AM | A | NR |
|
|
Mark J is the contact Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus * Plans currently in "review" status.
|