ELE12-03157
| ELE-Aging Inspection | 5/17/2016 | 5/17/2016 | 5/20/2016 3:28:10 PM | | CANC |
|
|
|
ELE16-01431
| Final | 5/17/2016 | 5/17/2016 | 5/17/2016 3:05:39 PM | P | PASS |
|
|
Call half hour before // Joe Phone #: ###-#### Final ok
|
ELE16-01569
| Permanent Service | 5/17/2016 | 5/17/2016 | 5/17/2016 2:36:56 PM | P | PASS |
|
|
Call before you come I''m doing a service change Phone #: ###-#### Inspection requested via web by Neal Rumsey Moving dryer, water heater circuit 12 ga shall fuse down or change. p/s o/h rec ok
|
ELE15-03901
| Electrical Rough-In | 5/17/2016 | 5/17/2016 | 5/17/2016 1:43:44 PM | P | PASS |
|
|
R/I of walls on 6th floor in NW corner of building, call Joey for inspection. Phone #: ###-#### Inspection requested via web by Rafael Castillo Noted on contractor print and in book in blue. wall rough in ok cover
|
ELE16-01512
| Electrical Rough-In | 5/16/2016 | 5/17/2016 | 5/17/2016 1:29:15 PM | A | PASS |
|
|
Asher Sears will be the electrician onsite Phone #: ###-#### Inspection requested via web by steve ragan Small TI to right of corridor wall rough in ok cover
|
ELE16-01513
| Electrical Rough-In | 5/16/2016 | 5/17/2016 | 5/17/2016 12:20:03 PM | A | PASS |
|
|
Asher Sears will be the electrician onsite. Phone #: ###-#### Inspection requested via web by steve ragan Corridor wall rough in ok cover
|
ELE16-01062
| Electrical Rough-In | 5/17/2016 | 5/17/2016 | 5/17/2016 11:15:05 AM | P | CANC |
|
|
We are requesting a wall rough-in inspection for this afternoon. Our contact is Rich @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate This permit for generator and epuipment related.
|
ESC16-00246
| Random Inspection | 5/17/2016 | 5/17/2016 | 5/17/2016 11:14:30 AM | P | PASS |
|
|
Landscape sub grade complete. OK
|
ELE16-01062
| Conference | 5/17/2016 | 5/17/2016 | 5/17/2016 11:12:56 AM | P | DONE |
|
|
We are requesting a wall rough-in inspection for this afternoon. Our contact is Rich @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Do to a change in gear required to complete install area created behind west gear which could entrap someone if fault occured. Contractor to install door on west side of gear and install panic hardware on all doors and all doors shall open out of electrical room new and existing. Other conference notes about generator and gear on permit number ELE15-03984.
|
ELE16-01491
| Electrical Rough-In | 5/17/2016 | 5/17/2016 | 5/17/2016 11:11:06 AM | P | PASS |
|
|
Wall rough in as noted on contractor print rough in ok cover
|
ELE16-01553
| Electrical Rough-In | 5/16/2016 | 5/17/2016 | 5/17/2016 10:02:04 AM | A | FAIL |
|
|
Inside walls Phone #: ###-#### Inspection requested via web by Jim Williams 210.64- A receptacle outlet shall be installed on rear of residence to serve as service receptacle for AC unit. 210.70(B)(2)- At least 1 outlet controlled by wall switch shall be install at outdoor entrances. 250.20- AC systems shall remain grounded. Install grounding electrode system to old service to provide ground until service change done.
|
ELE15-03682
| Electrical Rough-In | 5/16/2016 | 5/17/2016 | 5/17/2016 9:47:31 AM | A | CANC |
|
|
Please call 30min prior for access - Warren Phone #: ###-#### Upstairs rough in ok cover
|
ELE16-00957
| Final | 5/17/2016 | 5/17/2016 | 5/17/2016 8:32:01 AM | A | PASS |
|
|
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|