ELE16-03505
| Final | 5/16/2017 | 5/17/2017 | 5/17/2017 2:30:21 PM | P | FAIL |
|
|
Final remaining items on list. Contact is Kenny Williams ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves 110.26(D)- From previous conference which allowed motion detectors to be installed in equipment and electrical rooms because of manual control was provided integrated into switch. Code has been clearified due to unsafe operation of the automatic off function motion detector shall be removed in these areas. Manual only. 410.22- Site work included stone covering to be added to misc walls along walkways. Existing step lights remained but covers were lost leaving exposed wiring to be accessible to public. 2 rear, 1 front. * New walls were found in future TI on 3rd floor next to room 342, unable to locate permits for this space.
|
ELE17-01363
| Rough-In Permanent Service | 5/16/2017 | 5/17/2017 | 5/17/2017 10:50:46 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.52(I)- Entry way or foyer over 60 sq. ft. shall have a receptacle outlet installed on walls 3' wide or more. 240.24- Operating handle of a over current device shall not be higher than 6'7". 250.134- Metal box in net panel shall be connected to equipment grounding conductor. 300.4- NM coble shall be protected from physical damage where run thru bored hole that does not maintain 1 1/4" from framing surface. 10-3 below panel to left outer wall.
|
ELE17-01489
| Temporary Service | 5/16/2017 | 5/17/2017 | 5/17/2017 10:15:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk No pole present. Contractor believes may have called in wrong lot.
|
ELE17-01491
| Temporary Service | 5/16/2017 | 5/17/2017 | 5/17/2017 9:54:47 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE17-01490
| Temporary Service | 5/16/2017 | 5/17/2017 | 5/17/2017 9:54:04 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE17-00419
| Final | 5/16/2017 | 5/17/2017 | 5/17/2017 8:58:34 AM | A | PASS |
|
|
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine Final ok
|