BLD16-04504
| FIRE-Final Inspection | 5/17/2017 | 5/17/2017 | 5/18/2017 11:09:40 AM | P | FAIL |
|
|
Provide annual inspection for the existing fire extinguishers and add one in the back corridor. Provide testing for all of the exit signs and emergency lights.
|
NAF15-00032
| INSP-Final | 5/16/2017 | 5/17/2017 | 5/17/2017 3:11:39 PM | P | FAIL |
|
|
Seven of the eight 3rd floor apartments have smoke alarms too close to the bathroom doors. Provide documentation from the manufacturer that they are listed/approved for their current location or move to move than 3' as per NFPA 72. All other life safety items appear ok.
|
NAF17-00035
| INSP-Final | 5/17/2017 | 5/17/2017 | 5/17/2017 3:06:35 PM | P | PASS |
|
|
permit finaled
|
NAF17-00035
| INSP-Alarm Testing | 5/16/2017 | 5/17/2017 | 5/17/2017 3:06:16 PM | P | DONE |
|
|
Permit finaled
|
NAF16-00084
| INSP-Sprinkler Rough-in/Hydro | 5/17/2017 | 5/17/2017 | 5/17/2017 3:03:59 PM | P | PASS |
|
|
Overhead hydro test for the dry system passed
|
NAF16-00010
| INSP-Final | 5/15/2017 | 5/17/2017 | 5/17/2017 2:58:20 PM | P | PASS |
|
|
permit finaled
|
NAF16-00085
| INSP-Final | 5/16/2017 | 5/17/2017 | 5/17/2017 2:56:40 PM | P | PASS |
|
|
life safety passed
|
NAF16-00086
| INSP-Final | 5/16/2017 | 5/17/2017 | 5/17/2017 2:56:13 PM | P | PASS |
|
|
life safety passed
|
NAF16-00087
| INSP-Final | 5/16/2017 | 5/17/2017 | 5/17/2017 2:55:32 PM | P | PASS |
|
|
life safety passed
|
NAF16-00088
| INSP-Final | 5/16/2017 | 5/17/2017 | 5/17/2017 2:51:26 PM | P | PASS |
|
|
life safety passed
|
NAF15-00026
| INSP-Final | 5/16/2017 | 5/17/2017 | 5/17/2017 2:46:56 PM | P | PASS |
|
|
Life safety passed
|
FIR17-00235
| INSP-Final Inspection | 5/15/2017 | 5/17/2017 | 5/17/2017 2:31:48 PM | P | CANC |
|
|
No inspection performed. Need to wait until a FIR permit has been issued and an inspection scheduled for the interconnection of the hood suppression system to the existing riser monitoring system.
|
FIR16-00696
| INSP-Sprinkler Rough-in | 5/16/2017 | 5/17/2017 | 5/17/2017 10:23:29 AM | A | PASS |
|
|
The underground supply piping is ok to cover
|
FIR17-00097
| INSP-Sprinkler Rough-in | 5/16/2017 | 5/17/2017 | 5/17/2017 9:22:57 AM | A | PART |
|
|
The four pendant heads in the lay-in tile areas as marked on the plans are ok to cover. Also the 24 hour air test was started at 8:45am with 44psi on the guage
|
FIR16-00738
| INSP-Sprinkler Rough-in/Hydro | 5/16/2017 | 5/17/2017 | 5/17/2017 7:47:18 AM | A | PART |
|
|
Air test started at 7:30am with 43psi on both dry systems
|