Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04504 FIRE-Final Inspection5/17/20175/17/20175/18/2017 11:09:40 AMPFAIL
Provide annual inspection for the existing fire extinguishers and add one in the back corridor. Provide testing for all of the exit signs and emergency lights.
NAF15-00032 INSP-Final5/16/20175/17/20175/17/2017 3:11:39 PMPFAIL
Seven of the eight 3rd floor apartments have smoke alarms too close to the bathroom doors. Provide documentation from the manufacturer that they are listed/approved for their current location or move to move than 3' as per NFPA 72. All other life safety items appear ok.
NAF17-00035 INSP-Final5/17/20175/17/20175/17/2017 3:06:35 PMPPASS
permit finaled
NAF17-00035 INSP-Alarm Testing5/16/20175/17/20175/17/2017 3:06:16 PMPDONE
Permit finaled
NAF16-00084 INSP-Sprinkler Rough-in/Hydro5/17/20175/17/20175/17/2017 3:03:59 PMPPASS
Overhead hydro test for the dry system passed
NAF16-00010 INSP-Final5/15/20175/17/20175/17/2017 2:58:20 PMPPASS
permit finaled
NAF16-00085 INSP-Final5/16/20175/17/20175/17/2017 2:56:40 PMPPASS
life safety passed
NAF16-00086 INSP-Final5/16/20175/17/20175/17/2017 2:56:13 PMPPASS
life safety passed
NAF16-00087 INSP-Final5/16/20175/17/20175/17/2017 2:55:32 PMPPASS
life safety passed
NAF16-00088 INSP-Final5/16/20175/17/20175/17/2017 2:51:26 PMPPASS
life safety passed
NAF15-00026 INSP-Final5/16/20175/17/20175/17/2017 2:46:56 PMPPASS
Life safety passed
FIR17-00235 INSP-Final Inspection5/15/20175/17/20175/17/2017 2:31:48 PMPCANC
No inspection performed. Need to wait until a FIR permit has been issued and an inspection scheduled for the interconnection of the hood suppression system to the existing riser monitoring system.
FIR16-00696 INSP-Sprinkler Rough-in5/16/20175/17/20175/17/2017 10:23:29 AMAPASS
The underground supply piping is ok to cover
FIR17-00097 INSP-Sprinkler Rough-in5/16/20175/17/20175/17/2017 9:22:57 AMAPART
The four pendant heads in the lay-in tile areas as marked on the plans are ok to cover. Also the 24 hour air test was started at 8:45am with 44psi on the guage
FIR16-00738 INSP-Sprinkler Rough-in/Hydro5/16/20175/17/20175/17/2017 7:47:18 AMAPART
Air test started at 7:30am with 43psi on both dry systems