Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00120 INSP-Sprinkler Rough-in5/17/20175/17/20175/17/2017 4:00:34 PMPPART
Partial rough to cover inspection complete for the underground supply, straight sections of pipe approved for cover, all thrust blocks at changes of direction will be poured and inspected at a later date.
FIR17-00001 INSP-Sprinkler Rough-in/Hydro5/15/20175/17/20175/17/2017 3:58:38 PMPPART
Hydrostatic test for levels 1 and 2 complete. Rough to cover inspection complete for level 1, partial rough to cover inspection complete for level 2, levels 1 and 2 approved for cover except for the area's on level 2 where tenting still needs to be installed over fire sprinkler piping in attic spaces.
FIR16-00606 INSP-Sprinkler Rough-in5/17/20175/17/20175/17/2017 3:58:16 PMPPART
Rough to cover inspection complete for overhead fire sprinkler piping located east of the elevator lobby on level 2, all of level 2 approved for cover.
FIR17-00199 INSP-Final Inspection5/15/20175/17/20175/17/2017 2:27:57 PMPPASS
Final fire sprinkler inspection passed/complete
FIR17-00199 INSP-Sprinkler Rough-in5/15/20175/17/20175/17/2017 2:27:24 PMPPASS
Rough in inspection for overhead fire sprinklers complete
FIR16-00755 INSP-Sprinkler Rough-in/Hydro5/17/20175/17/20175/17/2017 12:01:44 PMPPART
Overhead hydrostatic test complete, noted that the garages have fire sprinkler piping/heads installed, some piping is located in attic spaces, this piping is tented with plastic sheeting but no insulation installed over the top, a minimum of R38 insulation needs to installed over fire sprinkler piping, fire sprinkler piping located in attic spaces in garages cannot be covered until insulation install is verified. The garages will need to have active conditioning installed to keep the fire sprinkler pipe/heads from freezing.
FIR16-00774 INSP-Sprinkler Rough-in/Hydro5/17/20175/17/20175/17/2017 11:59:44 AMPPASS
Overhead fire sprinkler piping hydrostatic test complete.
FIR17-00207 INSP-Final Inspection5/16/20175/17/20175/17/2017 11:20:14 AMAPART
Final inspection for door release complete, no automatic closer installed on the door at time of inspection (magnet released door but door would not close), after closer is installed/inspected for operation then permit can be signed off as complete.
FIR16-00088 INSP-Sprinkler Rough-in/Hydro5/17/20175/17/20175/17/2017 10:24:38 AMPPASS
24 hour air test on both dry systems complete
FIR16-00299 INSP-Sprinkler Rough-in5/16/20175/17/20175/17/2017 9:27:39 AMAPART
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in hotel resident rooms on level 10 complete, hotel resident rooms on level 10 approved for cover.
FIR16-00267 INSP-Sprinkler Rough-in5/15/20175/17/20175/17/2017 9:26:05 AMAPART
Rough to cover inspection for overhead fire sprinkler piping located above hardlids in the B side 3rd-6th floors complete (west wing) hardlids approved for cover.
FIR17-00001 INSP-Sprinkler Rough-in/Hydro5/15/20175/17/20175/15/2017 4:27:38 PMACANC
Call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello