ELE18-01204
| Electrical Rough-In | 5/17/2018 | 5/17/2018 | 5/17/2018 2:30:29 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid boarders only except break room rough in ok cover.
|
ELE18-00776
| Electrical Rough-In | 5/16/2018 | 5/17/2018 | 5/17/2018 10:44:15 AM | A | PASS |
|
|
Request is for ceiling inspection
Please contact Steve Nuxoll with any questions.
Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Entry and office grid, reception millwork Rough in ok cover. Discussed required clearances for transformer to wall, determined by manufacturers instructions if under 112KVA under 1000 volts. And system bonding jumper location for metallic raceway to be in transformer if equipment ground and system bonding present as per 450.10.
|
ELE18-01470
| Electrical Rough-In | 5/16/2018 | 5/17/2018 | 5/17/2018 9:14:32 AM | A | PASS |
|
|
Please call Corey Hayes Phone #: ###-#### Inspection requested via web by Kevin Perez Level 2 walls and hardlid rough in ok cover
|