Inspections for the day of: Tuesday, May 18, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00798 FIR-Aging Inspection5/18/20045/18/20045/18/2004 12:00:00 AM PASS
Project still under construction 5/18/2004 7:22:59 AM
FIR02-00133 INSP-Sprinkler Rough-in/Hydro5/12/20045/18/20045/18/2004 12:00:00 AMANR
Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Talked to Jim and he was not able to get the alarm company at the building but will reschedule when he can get all parties together to get the trip test done 5/18/2004 1:27:29 PM
BLD03-02579 FIRE-Final Inspection5/14/20045/18/20045/18/2004 12:00:00 AMAPART
Dado; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Temp occupancy approved pending deletion of Type I hood from approved 5/18/2004 10:07:44 AM
FIR04-00270 INSP-Sprinkler Rough-in5/17/20045/18/20045/18/2004 12:00:00 AMAPART
Contact - Mike Leiser -- UG Cover; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley UG okay to cover; will still need flush and hydro 5/18/2004 10:27:21 AM
MIS04-00137 FIR-Final5/17/20045/18/20045/18/2004 12:00:00 AMAFAIL
scott; Phone #: ###-#### Internet Inspection Request from: Annette Moore Hang K class extinguisher; sign above main exit; new appliances under Type I hood will require engineering for extinguishing system 5/18/2004 11:10:46 AM
MIS04-00138 FIR-Final5/17/20045/18/20045/18/2004 12:00:00 AMAFAIL
duane marler ###-#### --call 1st before insp for access Need exit signs at two designated exits in warehouse and emergency lighting; extinguishers need certification; keyed main exit in office door; landing at northeast warehouse exit; sign above main exit in office 5/18/2004 2:42:24 PM
MIS04-00066 FIR-Final5/17/20045/18/20045/18/2004 12:00:00 AMAPASS
FIR04-00141 INSP-Sprinkler Rough-in/Hydro5/17/20045/18/20045/18/2004 12:00:00 AMPPART
Contact Charles -- 200 lb hydro; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Hydro on wet system only - okay 5/18/2004 1:26:03 PM
FIR04-00141 INSP-Sprinkler Rough-in5/17/20045/18/20045/18/2004 12:00:00 AMPPART
Contact - Charles -- 24 Hour Air Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Start of 24 hr air test on dry system 5/18/2004 2:59:23 PM
FIR04-00069 INSP-Final Inspection5/18/20045/18/20045/18/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 5/18/2004 at 8:01:52 AM. Contact: ###-####. Sidewalls at north entry not installed so stopped inspection 5/18/2004 2:46:22 PM
FIR03-00693 INSP-Final Inspection5/18/20045/18/20045/18/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 5/18/2004 at 10:32:20 AM. Contact: ###-####. Need strobe lowered to 96 inches in conference room; update maps 5/19/2004 7:28:53 AM