Inspections for the day of: Wednesday, May 18, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00101 INSP-Final Inspection5/18/20055/18/20055/18/2005 4:26:34 PMPPASS
fire alarm finaled
FIR05-00112 INSP-Final Inspection5/17/20055/18/20055/18/2005 4:26:10 PMPFAIL
Not ready for final
BLD05-00333 FIRE-Final Inspection5/18/20055/18/20055/18/2005 3:59:06 PMPFAIL
Provide fire extinguisher and test access controled egress doors.
FIR05-00056 INSP-Final Inspection5/17/20055/18/20055/18/2005 2:33:09 PMPFAIL
no water to fill system to test alarms, need all items for final checked, need to flush underground. Pendant head inside is too close to trim work. No inspection done, these are just items on the way out.
BLD05-00767 FIRE-Final Inspection5/17/20055/18/20055/18/2005 1:52:50 PMPFAIL
Install missing canopies on the sprinkler pendants, test emergency lighting, exit signs and exit discharge lighting, provide verification duct smoke detector is existing and has had annual inspection or is not required.
MIS05-00029 FIR-Final5/18/20055/18/20055/18/2005 10:47:44 AMPPASS
Fire life safety finaled
FIR05-00241 INSP-Sprinkler Rough-in5/18/20055/18/20055/18/2005 10:20:16 AMPCANC
Wrong inspection called in. See fir05-00261
FIR05-00261 INSP-Sprinkler Rough-in5/18/20055/18/20055/18/2005 10:19:34 AMPPART
.Piping is ok to cover except two pendants need to be added just outside of the server room. I notified contractor that the shell permit will need to be finaled before tenant final is given
BLD04-02345 FIRE-Conference5/17/20055/18/20055/18/2005 10:03:56 AMADONE
fire conference//leonard; Phone #: ###-####
I went over fire dept access requirements with Leonard and gave him the copy of the approved drawings to keep for reference.
BLD05-00395 FIRE-Final Inspection5/18/20055/18/20055/18/2005 8:41:40 AMACANC
Need to get fire sprinkler finaled first but life safety is ready to final when fire sprinkler permit is finaled
FIR05-00097 INSP-Final Inspection5/18/20055/18/20055/18/2005 8:40:37 AMACANC
work is still in progress
FIR05-00096 INSP-Alarm Testing5/18/20055/18/20055/18/2005 8:39:55 AMAPASS
Fire alarm finaled